Using Intelligent Output Terminals
The intelligent output terminals are programmable in a similar way to the intelligent 
input terminals. The inverter has several output functions that you can assign individu-
ally to three physical logic outputs. Two of the outputs are open-collector transistors, and 
the third output is the alarm relay (form C – normally open and normally closed 
contacts). The relay is assigned the alarm function by default, but you can assign it to 
any of the functions that the open-collector outputs use.
L100 Inverter
12
11
CM2
Open collector outputs
Load
Load

+
Logic output 
common
L100 Inverter
12
11
CM2
Open collector outputs

+
Logic output 
common
RY
RY
Sinking Outputs,
Open Collector
The open-collector transistor 
outputs can handle up to 
50mA each. We highly 
recommend that you use an 
external power source as 
shown. It must be capable of 
providing at least 100mA to 
drive both outputs at full load. 
To drive loads that require 
more than 50mA, use external 
relay circuits as shown below.
Sinking Outputs,
Open Collector with
External Relays
If you need output current 
greater than 50mA, use the 
inverter output to drive a 
small relay. Be sure to use a 
diode across the coil of the 
relay as shown (reverse-
biased) in order to suppress 
the turn-off spike, or use a 
solid-state relay.