Step-by-Step Basic Installation
In
v
e
rt
er Mounting
and Installation
2–18
Wire the Inverter Output to Motor
Step 7: The process of motor selection is beyond the scope of this manual. However, it 
must be an AC induction motor with three phases. It should also come with a chassis 
ground lug. If the motor does not have three power input leads, stop the installation and 
verify the motor type. Other guidelines for wiring the motor include:
• Use an inverter-grade motor for maximum motor life (1600V insulation).
• For standard motors, use the AC reactor accessory if the wiring between the inverter 
and motor exceeds 10 meters in length.
Simply connect the motor to the terminals
[U/T1], [V/T2], and [W/T3] as shown to the 
right. This is a good time to connect the 
chassis ground lug on the drive as well. The 
motor chassis ground must also connect to 
the same point. Use a star ground (single-
point) arrangement, and never daisy-chain the 
grounds (point-to-point).
Use the same wire gauge on the motor and 
chassis ground wiring as you used on the 
power input wiring in the previous step. After 
completing the wiring:
• Check the mechanical integrity of each 
wire crimp and terminal connection.
• Replace the housing partition that covers 
access to the power connections.
• Close the main door and secure the reten-
tion screw firmly.
Logic Control Wiring
After completing the initial installation and powerup test in this chapter, you may need 
to wire the logic signal connector for your application. For new inverter users/applica-
tions, we highly recommend that you first complete the powerup test in this chapter 
without adding any logic control wiring. Then you will be ready to set the required 
parameters for logic control as covered in Chapter 4, Operations and Monitoring.