“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–10
Analog Input Settings
The inverter has the capability to accept an external analog input that can command the 
output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are 
available on separate terminals ([O] and [OI], respectively). Terminal [L] serves as 
signal ground for the two analog inputs. The analog input settings adjust the curve 
characteristics between the analog input and the frequency output.
In the graph below (left), A_13 and A_14 select the active portion of the input voltage or 
current range. The parameters A_11 and A_12 select the start and end frequency of the 
converted output frequency range, respectively. Together, these four parameters define a 
line segment as shown (below, right). When the line does not begin at the origin, A_15 
defines whether the inverter outputs 0Hz or the A_11 frequency when the analog input 
value is less than the A_13 setting (determines the non-linear part of the translation). 
A 12
A 11
A 13
A 14
A 12
A 11
A_15 = 00
A_15 = 01
A 13
A 14
Frequency
Frequency
0V
4mA
10V
20mA
% Input scale
% Input scale
0V
4mA
10V
20mA
0
0
%
%
“A” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FE 
(CE)
–FU 
(UL)
–FR 
(Jpn)
Units
A_11 O–L input active range 
start frequency
The output frequency corre-
sponding to the analog input 
range starting point
0.0
0.0
0.0
Hz
IN EXS   000.0Hz
A_12 O–L input active range 
end frequency
The output frequency corre-
sponding to the analog input 
range ending point
0.0
0.0
0.0
Hz
IN EXE   000.0Hz
A_13 O–L input active range 
start voltage
The starting point (offset) for 
the active analog input range
0
0
0
%
IN EX%S     000%
A_14 O–L input active range 
end voltage
The ending point (offset) for 
the active analog input range
100
100
100
%
IN EX%E     100%
A_15 O–L input start 
frequency enable
Two options; select codes:
00 ...Use offset (A_11 value)
01 ...Use 0 Hz
01
01
01
IN LEVEL     0Hz