“B” Group: Fine Tuning Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–26
Software Lock Mode
The software lock function keeps personnel from accidentally changing parameters in 
the inverter memory. Use B_31 to select from various protection levels.
The table below lists all combinations of B_31 option codes and 
the ON/OFF state of the [SFT] input. Each Check 
✔ or Ex ✘ 
indicates whether the corresponding parameter(s) can be edited. 
The Standard Parameters column below shows access is permit-
ted for some lock modes. These refer to the parameter tables 
throughout this chapter, each of which includes a column titled 
Run Mode Edit as shown to the right. The marks (Check 
✔ or 
Ex 
✘) under the “Run Mode Edit” column title indicate whether access applies to each 
parameter as defined in the table below. In some lock modes, you can edit only F_01 and 
the Multi-speed parameter group that includes A_20, A220, A_21–A_35, and A_38 
(Jog). However, it does not include A_19, Multi-speed operation selection. The editing 
access to B_31 itself is unique, and is specified in the right-most two columns below.
NOTE: Since the software lock function B_31 is always accessible, this feature is not 
the same as password protection used in other industrial control devices.
B_31 
Lock 
Mode
[SFT] 
Intelligent 
Input
Standard Parameters
F_01 and 
Multi-Speed
B_31
Stop
Run
Stop & Run
Stop
Run
00
OFF
Run mode 
edit access
ON
01
OFF
Run mode 
edit access 
ON
02
(ignored)
03
(ignored)
Run 
Mode 
Edit