Installation
 
900-0111-01-00 Rev A 
19
 
DC Wiring
     
 
 
 
CAUTION:  Equipment Damage 
Never reverse the polarity of the battery cables.  Always use correct polarity. 
 
CAUTION:  Fire Hazard 
Always install a breaker, fuse, or protective device to protect the DC system.  
Table 4 
DC Conductor Size and Torque Requirements
      
 
Inverter   Nominal DC Amps
(Derated 125%)
 
Conductor Size  
(Minimum)
 
Breaker Size
GFX1312E 
130 
70 mm2 (2/0 AWG or 0.105 in2) 
175 Adc 
GFX1424E 
70 
70 mm2 (1/0 AWG or 0.083 in2) 
125 Adc 
GFX1448E 
35 
50 mm2 (#1 AWG or 0.066 in2) 
100 Adc 
Terminal Location 
Torque Requirements 
Inverter DC Terminals
 
4 Nm (35 in-lb) 
Battery Terminals
 
See battery manufacturer’s recommendations 
When installing DC cables: 
  Note minimum sizes in Table 4, but refer to local codes for absolute cable size recommendations. 
  Battery positive and negative cables should be no longer than 3 meters (10 feet) each, to minimize voltage 
loss and other effects. 
  Always install breakers or fuses on the positive cable. 
  The cables listed above are for each inverter in a system.  In a system with multiple inverters, each inverter 
requires its own cables and breakers of the size indicated. 
  The inverter’s battery terminal is a threaded stud which accepts a ring terminal lug.   Use crimped and sealed 
copper ring lugs with 0.79 cm (5/16 in) holes, or use compression lugs. 
  Tie, tape, or twist cables together to reduce self-inductance.  Run positive and negative cables through the 
same knockouts and conduit. 
  Make certain the DC breaker is turned to the off position, or the fuse is removed, before proceeding. 
 
 
Figure 8 
Battery Terminal Covers 
 
 
If present, remove the battery 
terminal covers.  These are made of 
stiff plastic with a snap-on design.  
Remove carefully using a flat 
screwdriver inserted into the slots 
on the sides of each cover.