V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
60-2309—1
3
6
Fig. 3. 7616BR Damper Crank Arm can be attached to 
actuator shaft to drive a damper when valve is open.
WIRING
WARNING
Electrical Shock Hazard.
Can cause serious injury or death.
Disconnect power supply before making wiring 
connections to prevent electrical shock and equipment 
damage.
Wiring must comply with all applicable electrical codes, 
ordinances and regulations. Wiring to the actuator must be 
NEC Class 1.
Connect the power supply to terminals 1 and 2 on the V4055 
terminal strip. Refer to Fig. 4 for Auxiliary Switch connections 
and Fig. 5 for Max Flow Limit Switch connections. For typical 
system hookups, refer to Fig. 6 and to instructions packed with 
the device used to control the valve. 
When all wiring connections are complete, replace the actuator 
faceplate.
CAUTION
Operation Hazard.
Improper wiring can cause improper and 
dangerous operation.
Label all wires prior to disconnection when servicing 
valves. Wiring errors can cause improper and 
dangerous operation.
NOTE: Pipe sealant is required on the conduit threads of 
actuators with NEMA 4 enclosures.
Adjust Auxiliary Switch (If Used)
The Auxiliary Switch is adjustable throughout the stroke of 
the actuator. With the switch installed in the actuator, turn
the adjusting screw (see Fig. 2) clockwise  
 to cause the 
switch to operate earlier in the stroke or counter-
clockwise
 to cause the switch to operate later in the 
stroke.
Fig. 4. External connections to the V4055 Actuator.
Fig. 5. Connecting the Max Flow 
Limit Switch to the actuator.
NOTE: The Proof-of-Closure Switch is not adjustable.
Adjust Max Flow Limit Switch (If 
Used)
The Max Flow Limit Switch is adjustable throughout the stroke 
of the actuator. With the switch installed in the actuator, turn 
the adjusting screw clockwise
 to cause the switch to 
operate earlier in the stroke or counter-clockwise
 to 
cause the switch to operate later in the stroke.
52 DEGREE
ANGULAR
ROTATION
MAXIMUM
TRAVEL
SHAFT
7616BR
DAMPER 
ARM
M7322
RADIUS
2-11/16  (68.3)
2-5/16  (58.7)
1
2
3
2
1
1
2
AUXILIARY
SWITCH
L1
HOT
L2
POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND 
DISCONNECT MEANS AS REQUIRED.
SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN 
VALVE IS SHUT (DE-ENERGIZED).
3
SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN 
VALVE IS SHUT (DE-ENERGIZED).
NO
NC
C
NO
NC
C
PROOF-OF-CLOSURE
SWITCH
2
3
M7334
M12798
C
7800 SERIES
RELAY 
MODULE
NC
NO
ADJUSTABLE
MAX 
FLOW
LIMIT 
SWITCH
FIELD WIRING
INTERNAL WIRING
TRAVEL
LIMIT
SWITCH
PUMP
MOTOR
PUMP
VALVE
1
L2
9
2
3
4