TECHNICIAN’S QUICK REFERENCE GUIDE
69-1957—1
L7224 Series
Oil Electronic 
Aquastat® Controller
The following service procedure provides a quick overview for 
L7224 Series Controllers. For more information, refer to form 
69-1384.
On the L7224U the High Limit, High Limit Differential, Low Limit, 
and Low Limit Differential can be adjusted to the settings 
recommended by the boiler OEM.
Adjusting Settings
To discourage unauthorized changing of Aquastat® settings, a 
procedure to enter the adjustment mode is required. To enter the 
adjustment mode, press the UPDOWN, and I buttons 
simultaneously for three seconds. Press the I button until the 
feature requiring adjustment is displayed:
HL—High Limit.
LL—Low Limit.
Ldf—Low Limit differential.
F - C—°F or °C.
Then press the UP and/or DOWN buttons to move the set point to 
the desired value. After 60 seconds without any button inputs, the 
control will automatically return to the READ mode.
To use the L7224U in a cold start boiler application, disable the 
Low Limit function by pressing the UP arrow button, DOWN arrow 
button and I buttons simultaneously for three seconds. Then push 
the I button until LL is displayed. Then press the down arrow 
button until OFF is displayed.
Display
In the RUN mode, the Aquastat® will flash “bt” (boiler temp) 
followed by the temperature (i.e., 220), followed by °F or °C.
To read boiler settings, press the I key to read the parameter of 
interest. For example, press I (HL) High Limit is displayed, 
followed by a three-digit number, i.e., 220, followed by °F or °C. 