Master Programming Level
Programming
The following examples show the editing of a photoelectric smoke detector with address 017, 
located on the first SLC loop:
Enable/Disable Detector
To Enable or Disable the detector, press the 1 key while viewing the Edit Detector Screen #2.  Each 
press of the key will toggle the screen between Enabled Yes and Enabled No.  If Enabled No is 
selected, the detector will not be polled by the control panel, preventing the detector from reporting 
alarms and troubles to the panel.  The control panel will display the device type and address which 
has been disabled and will turn on the Trouble LED and Disable LED.
Type
To select the type of detector being programmed, press the 2 key while viewing the Edit Detector 
Screen #2.  This will cause the control panel to display the following Detector Type Screens:  
EDIT DETECTOR 1D017
1=ENABLED        YES
2=TYPE  SMOKE(PHOTO)
3=VERIFICATION   OFF
Edit Detector Screen #2
EDIT DETECTOR 1D017
1=WALKTEST        NO
2=PAS             NO
3=PRE-SIGNAL      NO
Edit Detector Screen #3
EDIT DETECTOR 1D017
1=ZONE ASSIGNMENT
    00 ** ** ** **
Edit Detector Screen #4
Edit Detector Screen #5
EDIT DETECTOR 1D017
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
EDIT DETECTOR
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Detector Screen #2
   DETECTOR TYPE
1=SMOKE PHOTO
2=USER DEFINED-1
3=SMOKE (ION)
Detector Type Screen #1