2. Low Ice Production
Problem
Possible Cause
Remedy
[1] Low ice production.
a)Evaporator
1. Dirty.
1. Clean. See "VI.A. 
Cleaning and Sanitizing 
Instructions."
b)Bin Control
1. Erratic, sticking, 
defective.
1. See "IV.D. Bin Control 
Check."
c) Losing Water
1. Drain valve leaking.
1. Clean or replace.
. Mechanical seal 
leaking.
. Replace.
3. O-ring leaking.
3. Replace.
d)Expansion Valve (TXV) 
(not adjustable)
1. Low-side pressure too 
low.
1. Replace.
. Low-side pressure too 
high.
. See if expansion valve 
bulb is mounted properly, 
and replace the valve if 
necessary.
e)Refrigerant Line
1. Gas leaks.
1. Check for leaks with a leak 
detector. Repair leaks. 
Replace drier and charge 
with refrigerant. See "V.A. 
Service for Refrigerant 
Lines."
. Refrigerant lines or 
components restricted
. Remove the restriction or 
component and replace 
the drier.
3. Overcharged.
3. Recharge.
f) High-Side Pressure 
Too High
1. Dirty air filter or 
condenser. 
1. Clean.
. Ambient or condenser 
water temperature too 
warm. 
. Reduce temperature.
3. Fan motor slow rpm.
3. See "3.[]a) Fan Motor".
4. Fan motor capacitor.
4. Check and Replace.
5. Condenser water 
pressure too low or off 
(water-cooled model).
5. Check and get 
recommended pressure.
6. Water regulating 
valve restricted 
(water-cooled model).
6. Clean.
g)Compressor
1. Inefficient compressor. 1. Replace compressor.
. Faulty thermal 
protector (overload).
. Replace compressor.
3. Faulty capacitor/
starter.
3. Replace components.