National Instruments 800 Series 사용자 설명서

다운로드
페이지 104
© National Instruments Corporation
C-1
Appendix
C
LED Indicators
This appendix describes how to read the LEDs on the front panel to 
interpret the status of the VXIpc 800 Series.
VXIbus Interface Status LEDs
The VXIbus interface status LEDs are located at the top of the module 
and include four LEDs: FAILEDSYSFAILONLINE, and TEST
They indicate the various stages of initialization that occur as the 
VXIpc 800 boots. The following paragraphs describe each LED.
SYSFAIL LED
The SYSFAIL LED is lit when the VMEbus SYSFAIL signal is 
asserted. It does not necessarily indicate that the VXIpc 800 is asserting 
SYSFAIL, only that there is a device in the system asserting SYSFAIL.
FAILED LED
The FAILED LED is lit when the VXIpc 800 is driving the SYSFAIL 
signal. The VXIpc 800 asserts SYSFAIL when the PASSED bit in its 
VXIbus status register is clear. The PASSED bit is set by the power-on 
self configuration circuitry (POSC) when it has completed initializing 
the VXIbus interface.
ONLINE LED
The ONLINE LED is lit when the Resource Manager has successfully 
completed and the VXIbus interface is ready for application programs.
TEST LED
The TEST LED is lit when the power-on self configuration circuitry is 
configuring the VXIbus interface.