DMP Electronics XR500 사용자 설명서

다운로드
페이지 84
XR500 Series Canadian Programming Guide 
Digital Monitoring Products
13
neTwork oPTionS
Network Options 
(XR500N/XR500E only)
Network Options are provided to define the network configuration for the panel. This information will be
used during communication of messages via network or email.
Note: IP addresses and port numbers may need to be assigned by the network administrator. When
entering an IP, Gateway, or Subnet Mask address be sure to enter all 12 digits and leave out the periods.
For example, IP address 192.168.000.250 is entered as 192168000250.
4.1 
DHCP   
 NO YES
 DHCP Mode Enabled
If the panel uses a dynamic IP address select YES. When set to YES, the panel
operates using DHCP and does not use the Local IP Address number. When the DHCP
option is set to NO, the panel uses the IP address entered in Local IP Address. The
default value for DHCP mode is YES.
4.2 
LOCAL IP ADDRESS
 Local IP Address
          192.168.0.250
 
Enter the local IP address. The Local IP Address must be unique and cannot be
duplicated. The default local IP address is 192.168.0.250.
4.3 
GATEWAY ADDRESS
 Gateway Address
              192.168.0.1
 
Enter the local gateway address. The Gateway IP Address is needed to exit your
local network. The default gateway address is 192.168.0.1.
4.4 
SUBNET MASK
 Subnet Mask
     255.255.255.000
 
Enter the local subnet mask assigned to the panel.  The default subnet mask address 
is 255.255.255.000. 
4.5 
DNS SERVER
 DNS Server 
 
              192.168.0.1
 
Enter the IP address of the DNS (Domain Name System) used by the panel to resolve
domain names into IP addresses. The default address is 192.168.0.1.
4.6 
PASSPHRASE
-
 Passphrase
 (XR500E only)
To enable encryption type an 8 to 16-character Passphrase using alphanumeric
characters.  If you leave the Passphrase blank, the panel communicates with the 
SCS-1R Receiver, but the data is not encrypted. The Passphrase is blank by default.
The XR500E panel is capable of communicating encrypted data to an SCS-101
Network Line Card installed at the receiver. The XR500E panel and the SCS-101 must
have the same secret password called a Passphrase.    
 
Note: DO NOT LOSE THE PASSPHRASE.  A lost or forgotten Passphrase requires that 
the XR500E panel and every iCOM-E unit reporting in to the same iCOM-E unit at the
receiver be individually reprogrammed with a new passphrase.
Note:  An XR500E panel communicates using AES encryption.  If you currently have 
an XR500N panel installed, you may purchase a separate feature key to activate 
encrypted communications using the Feature Upgrade process described in the 
Feature Upgrade Section.  Encrypted communication cannot be enabled on a 
standard XR500 panel.