Eleven (11) wires should be run from thermostat 
subbase to the 24V terminal board in the unit.  An 
eleven conductor, 18 gauge copper color-coded 
thermostat cable is recommended.  The connection 
points are shown in Figure 11.  An additional wire is 
needed if dehumidification is used.
table  3
thermOstat WIre sIZe
ImPOrtant
Only the thermostat combinations as shown 
above will work with this equipment.
transformer 
Va
Fla
Wire Gauge
maximum
Distance 
In Feet
65
2.3
20 gauge
45
18 gauge
60
16 gauge
100
14 gauge
160
12 gauge
250
#8403-052, 8403-053, 8403-055
Y
DH
THERMOSTAT
BARD PART #8403-060
G
L
Y1
W1/E
R
O/B
W2
A
AUX
UNIT LOW VOLTAGE
TERMINAL BLOCK
THERMOSTAT BARD PART 
B
L
E
W3
W2
W1
Y1
Y2
D/YO
R
G
C
O1
W1
B
Y2
Y1
Rh
Rc
G
C
C
Factory Jumper
1
GND
MIS-2026 C
ID
GND
OD
OPTIONAL
8403-061
OUTDOOR
SENSOR
OPTIONAL
8403-062
INDOOR
SENSOR
FIGure  11
unIt 24V thermOstat cOnnectIOns
WIrInG  –  maIn POWer
Refer to the unit rating plate for wire sizing information 
and maximum fuse or “HACR” type circuit breaker 
size.  Each outdoor unit is marked with a “Minimum 
Circuit Ampacity”.  This means that the field wiring 
used must be sized to carry that amount of current. 
Depending on the installed KW of electric heat, there 
may be two  field power circuits required.  If this is the 
case, the unit serial plate will so indicate.  All models 
are suitable only for connection with copper wire.  Each 
unit and/or wiring diagram will be marked “Use Copper 
Conductors Only”.  These instructions 
must be adhered 
to.  Refer to the National Electrical Code (NEC) for 
complete current carrying capacity data on the various 
insulation grades of wiring material.  All wiring must 
conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C 
copper) for all models including the most commonly 
used heater sizes.  Also shown are the number of field 
power circuits required for the various models with 
heaters.
The unit rating plate lists a “Maximum Time Delay 
Relay Fuse” or “HACR” type circuit breaker that is to 
be used with the equipment.  The correct size must be 
used for proper circuit protection and also to assure that 
there will be no nuisance tripping due to the momentary 
high starting current of the compressor motor.
The disconnect access door on this unit  may be locked 
to prevent unauthorized access to the disconnect.  To 
convert for the locking capability, bend the tab located 
in the bottom left hand corner of the disconnect 
opening under the disconnect access panel straight 
out.  This tab will now line up with the slot in the door.  
When shut, a padlock may be placed through the hole 
in the tab preventing entry.
See “Start Up” section for important information on 
three phase scroll compressor start ups.
WIRING  –  LOW VOLTAGE WIRING 
230 / 208V, 1 phase and 3 phase equipment have 24V 
transformers with dual primary voltage.  All equipment 
leaves the factory wired on 240V tap.  For 208V 
operation, reconnect from 240V to 208V tap.  The 
acceptable operating voltage range for the 240 and 208V 
taps are:
 
taP ranGe
 
240 
253 – 216
 
208 
220 – 187
NOTE: 460V units require no action.  The voltage    
should be measured at the field power
connection point in the unit and while the unit is
 
operating at full load (maximum amperage    
 
operating condition).
FIGure  10
cOmmOn Wall mOuntInG InstallatIOns
Outside Wall
Closet Wall 
Closet Wall 
Grille
Return Air
Return Air
Supply Air
Duct
Finished Ceiling
Raised Closet Floor 
Rafters
Wall Sleeve
Closet Installation
Unit (outside)
Note: duct maybe in attic or 
below rafters as shown.
MIS-2240
Grille
 Only needed if dehumidification is used.