Snorkel Terminations
For installations requiring a vertical rise on the exterior of the building, 
14­inch and 36­inch tall snorkel terminations are available.  When us­
ing a snorkel, the stove can be vented directly out the back. There is a 
vent starter collar fastened to the stove (to vent straight out the back), 
remove the four screws securing the collar, rotate the collar 180 degrees 
and refasten using the same four screws. Make sure the gasket between 
the collar and the stove is properly positioned before refastening the 
collar. After rotating the collar, it will be positioned horizontally.  When 
this pipe passes through a wall, a wall thimble ­ Simpson part number 
942or Security™ part number SV4RSM is required. The hole in the wall 
for the wall thimble should be 9­1/4” wide by 10­1/4” high. To vent out 
the rear wall, add up to a 12” section of pipe and then the snorkel. When 
the stove is located in a corner of the room, to vent horizontally first 
add a 45 degree elbow, then up to a 12” section of pipe and lastly the 
snorkel. Installations using a snorkel have no restrictor installed in the 
pipe (see Pages 15 and 16 for restrictor positioning).    Follow the same 
installation procedures as used for standard horizontal terminations.  If  
the snorkel termination  must be installed below grade, (i. e. basement 
application), proper drainage must be provided to prevent water from 
entering the snorkel.  Do not attempt to enclose the snorkel within the 
wall, or any other type of enclosure. On vinyl siding, furring strips may 
be used to ensure that the snorkel is not recessed into the siding.
Framed Hole: 9-1/4” 
Wide by 10-1/4” High
Wall Thimble 
Elbow
Termination Cap 
A Minimum of 18” Sec-
tion of Pipe
Wall Thimble 
Framed Hole:
9-1/4”x 10-1/4”
High
Snorkel 
Vertical Vent Installation
Important Notes
1. All vertically terminated vent installations use 6­5/8”x 4” Se­
curity™ Secure Vent™ pipe*.
2. If the vent passes through a ceiling or floor, a firestop ­ Simpson 
#963 or Security™ #SV4BF ­  is required.
3. If the vent passes through the roof, a roof flashing ­ Simpson 
#943 or 943S or Security™ #SV4FA or SV4FB ­ and storm collar 
­  Simpson #953 or Security™ #SV4FC ­ are required.
4. A 1­inch clearance from the vent pipe to combustible materials 
must be maintained.
5. A maximum of either two 45º elbows or two 90º elbows may 
be used. See diagrams showing allowable offsets.
6. The maximum system height is 30 feet and the minimum is 10 
feet.
Pipe Length 
Vertical Termination Cap  
Storm Collar 
Flashing  
Roof - Maintain 1”
Clearance to Combustibles 
Ceiling Minimum 
Framing 10”x 10” 
Ceiling Firestop  
Figure 20
Figure 21
Figure 22