Combustion Analysis Procedure
1.  Turn the main power off to the boiler by placing the 
“On/Off” switch in the OFF position.
2.  Remove the flue temperature sensor from the flue pipe 
connection.  Note:  Combustion measurements will be 
made at this point.
3.  Turn the main power on to the boiler by placing the 
“On/Off” switch in the ON position.
4.  Place the boiler into the active position by pressing the 
RIGHT SELECT [ON] key (see page 7).
5.  Locate the pinhole button below the RESET button on 
the display board (see page 7).  Insert a thin wire (such 
as a paper clip) into the hole and press the button once 
and hold for 5 seconds to place the boiler into Service 
Mode.  In Service Mode the boiler will fire at ignition 
speed and will then modulate up to full fire.
6.  Insert the probe from a combustion analyzer into the 
hole left by the removal of the flue temperature sensor.
7.  Once the boiler has modulated up to full fire, measure 
the combustion.  The values should be in the range 
listed in Table 3-5 above.  The CO levels should be less 
than 150 ppm for a properly installed unit.
 
If the combustion is not within the specified range, 
reference the chart below for possible causes and 
corrective actions.
Table 3-5 Flue Products
Natural Gas
Propane
CO
2
O
2
CO
2
O
2
8.0% - 10%
3.0% - 6.5%
9.0% - 11%
4.1% - 6.9%
8.  Once the combustion analysis is complete, test the safety 
 
shutoff device by turning the manual shutoff switch to 
 
the OFF position and ensuring that the boiler shuts 
 
down and registers an alarm.  Turn the manual shutoff 
 
switch to the ON position, reset the control, and return 
 
to Service Mode.
9.  Turn the main power off to the boiler and replace the flue 
 
temperature sensor into the flue pipe connection.
10.  Place the boiler back into normal operation.
You must replace the flue gas temperature 
sensor to prevent flue gas spillage into 
the room.  Failure to comply could 
result in severe personal injury, death, or 
substantial property damage.
 WARNING
Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface 
FAULT
DESCRIPTION
CORRECTIVE ACTION
Low 24 vac
120 vac input to the main control board has 
dropped below 80 vac.
•  Check 120 vac supply to the transformer.
• Check wiring connections at the low voltage 
 terminal 
strip.
•  Check the wire size/length to remote devices.
•  Replace the transformer.
Watch Dog Error
The main control board has detected an 
internal fault.
•  Replace the main control board.
Write EEProm
The main control board has detected an 
internal fault.
•  Replace the main control board.
CRC Parameters
The main control board has detected an 
internal fault.
•  Replace the main control board.
No Error Stored
The main control board has detected an 
internal fault.
•  Replace the main control board.