DH90 Dehumidifier • For HVAC Installer Only
10
9.1 Troubleshooting
No dehumidification, neither fan nor compressor 
run with fan switch and ventilation timer OFF.
1.  Unit unplugged or no power to outlet.
2.  Humidity control set too high or defective.
3.  Loose connection in internal or control wiring.
4.  Defective Compressor relay.
5.  Defective control transformer.
6.  Low pressure control open.
7.  Optional Condensate Pump Safety Switch 
open.
No dehumidification, compressor does not run 
but fan runs when there is a call for dehumidi-
fication and the ventilation control is OFF.
1.  Defective compressor run capacitor.
2.  Bad connection in compressor circuit.
3.  Defective compressor overload.
4.  Defective compressor.
5.  Defrost thermostat open.
6.  Optional Condensate Pump Safety Switch 
open.
Fan runs when there is a call for dehumidifica-
tion and the ventilation control is OFF, but the 
compressor cycles on and off too frequently. 
1.  Low ambient temperature and/or humidity 
causing unit to cycle through defrost mode.
2.  Defective compressor overload.
3.  Defective compressor.
4.  Defrost thermostat defective.
5.  Dirty air filter(s) or airflow restricted.
6.  Low refrigerant charge, causing defrost 
control to cycle.
7.  Bad connection in compressor circuit. 
Fan does not run with fan switch in either 
position.
9. Service
CAUTION: Servicing the DH90 with its high pressure refrigerant system and high voltage circuitry 
presents a health hazard which could result in death, serious bodily injury, and/or property damage. 
Service should only be performed by a qualified service technician.