L8124A,C,E,L AND M AQUASTAT® RELAYS
7
95-6571—11
Fig. 11. L8124L multizone system with circulator connections and internal schematic.
OPERATION
High Limit Controller
The high limit opens and turns off the burner when the 
water temperature reaches the setpoint. The high limit 
automatically resets after the water temperature drops 
past the setpoint and through the 10°F (6°C) differential.
WARNING
Explosion Hazard.
Can cause serious injury, death or equipment 
damage.
Use this product only in systems with a pressure 
relief valve.
Low Limit and Circulator Controllers
On a temperature rise, with the adjustable differential at 
the minimum setting of 10°F (6°C), the burner circuit 
(R-B) breaks and the circulator circuit (R-W) makes at 
the control setpoint. On a temperature drop of 10°F (6°C) 
below the setpoint, the R-B circuit makes and the R-W 
circuit breaks. See Fig. 12.
At any differential setting greater than 10°F (6°C), the 
R-B make temperature and the R-W break temperature 
remain the same (control setting minus 10°F [6°C]). The 
R-B break and R-W make temperature are the setpoint 
temperature plus the difference between the differential 
setting and 10°F (6°C).
EXAMPLE: Setpoint of 140°F (60°C), differential set 
at 25°F (14°C). On a temperature rise, R-B breaks 
and R-W makes at 155°F (68°C). On a temperature 
fall, R-B makes and R-W breaks at 130°F (54°C).
Fig. 12. Relationship of setpoints and differential.
M8829
L1 
(HOT)
L2
1
3
1
2
3
2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 
OVERLOAD PROTECTION AS REQUIRED.
CONTROL CASE MUST BE CONNECTED TO EARTH 
GROUND. USE GROUNDING SCREW PROVIDED.
B1 IS 1/4 IN. TAB TERMINAL.
2
1
4
3
5
6
LOW VOLTAGE
THERMOSTAT
ZONE 1
ZONE 2
LOW VOLTAGE
THERMOSTAT
R845A RELAY ZONE 2
ZONE 2
CIRCULATOR
TO ADDITIONAL
R845A RELAYS
FOR OTHER ZONES
LINE VOLTAGE
OIL BURNER
RELAY OR
GAS VALVE
LINE VOLTAGE
CIRCULATOR
ZONE 1
B2
C2
C1
ZR
B1
R
B
HIGH 
LIMIT
Z
1K1
B
R
W
LOW LIMIT/
CIRCULATOR
1K
2
1
G
T
TV
L8124L
1K2
ZC
LOW LIMIT 
AND 
CIRCULATOR
SETTING
HIGH LIMIT
SETTING
SWITCH BREAKS ON 
TEMPERATURE RISE. 
BURNER TURNS OFF. 
CIRCULATOR OPERATES 
ON A CALL FOR HEAT.
SWITCH MAKES ON 
TEMPERATURE FALL.
BURNER OPERATES ON A 
CALL FOR HEAT.
SWITCH MAKES R-W 
AND BREAKS R-B ON 
TEMPERATURE RISE.
SWITCH MAKES R-B AND 
BREAKS R-W ON 
TEMPERATURE FALL. 
BURNER IS ON TO 
MAINTAIN MINIMUM 
WATER TEMPERATURE. 
CIRCULATOR IS OFF.
M1523
SWITCH MAKES R-W 
AND BREAKS R-B ON 
TEMPERATURE RISE.
WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER 
SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING 
FOR HEAT).