Generac 005415-0 사용자 설명서

다운로드
페이지 56
 22 
Figure 1.3 - Connection for 120/240 Volts
T1
RED
T2
WHITE
T3
BLACK
GROUNDED NEUTRAL
STATOR POWER
WINDINGS
CB1
CB2
The AC connection system on air-cooled generators uses a 
• 
GROUNDED neutral.
A separate green ground wire is connected to the recreational 
• 
vehicle’s junction box.
Total load connected across T1 (Red) to T2 (White), and T3 
• 
(Black) to T2 (White), must not exceed rating for the specific 
generator (see "Generator Specifications").
NOTE:
Do NOT connect loads in excess of circuit breaker ratings.
2.1   LOCATION AND SUPPORT
2.1.1 GENERATOR 
LOCATION
NOTE
Be sure the installation complies with all standards and codes 
listed in the "Standards Booklets" section of this manual.
The most desirable location for the generator set is between the 
vehicle's main frame members. However, this is seldom possible. 
Most units must be installed on the side of the vehicle and are 
difficult to reinforce.
Many recreational vehicles have been factory equipped with an 
area for the generator set. Some vehicles may even have a genera-
tor compartment provided by the vehicle manufacturer.
Plan the generator location based on the following:
The generator set must be installed on a framework that is 
• 
part of the recreational vehicle, as outlined in the "Generator 
Support" section.
The location must provide an access opening that is large 
• 
enough to permit generator removal (unless the generator is to 
be removed from underneath the supporting framework).
The location must provide easy access to frequently serviced 
• 
components, such as filters, oil drains, spark plugs and other 
common maintenance parts.
The location must provide sufficient room to allow minimum 
• 
clearances as outlined in "Generator Compartments". If sound 
insulation is to be used on the compartment walls and ceiling, 
the minimum recommended applies to the space between the 
generator and such insulation.
The location must provide adequate cooling and ventilating 
• 
airflow for the generator without a great deal of work and 
expense.
If mounting the generator in an enclosed compartment, the base 
• 
of the generator must rest flat on the floor without any gaps.
When using a suspended mounting system, ensure the base of 
• 
the generator is flush with the surrounding bodywork. If the unit 
is mounted higher in the structure, heated air may recirculate 
into the generator causing it to overheat.
2.1.2 GENERATOR 
SUPPORT
The generator must be securely attached to a metal framework that 
has been made part of the vehicle frame structure by bolting or 
welding. The metal framework on which the generator will rest and 
which will restrain the generator set should consist of at least two 
horizontal beams. These beams should consist of (a) 1-1/2-inch 
square, 11-gauge steel tubing OR (b) 1-1/2-inch, 11-gauge angle 
iron. A typical supporting frame with horizontal support tubing, is 
shown in Figure 2.1.
Figure 2.1 – Typical Horizontal Support Frame
The generator can be installed so that it sits on top of the horizontal 
support tubing if the vehicle design permits. Another method is 
to suspend the generator below the horizontal support tubing by 
means of suitable, structurally sound metal framework. The fol-
lowing general rules apply:
Vehicle construction MUST be capable of supporting the weight 
• 
of the generator.
Whether the generator is mounted above the horizontal support 
• 
tubing or suspended below the tubing, the supporting frame 
used must be structurally sound.
If the generator cannot be bolted directly to the supporting 
• 
frame or support tubing, consider using additional tubing, 
angle brackets or other supports to give the supporting frame 
sufficient strength.
Installation