Puls UB10.241 UPS 사양 가이드

다운로드
페이지 23
 
 
 
UB10.241 
 
  USeries 
24V, 10A, DC-UPS 
 
 
 
Fig. 13-1   Contact control drawing for use in Haz-Loc 
environments 
 
 
 
12/23 
+ -
Ready
DC- 
UPS
1
Hazardous 
Location
Non Hazardous 
Location
Apparatus
Voc
Isc
Input
Output
+ -
+
-
Battery
Buffering
Voc
Isc
Replace 
Battery
Voc
Isc
2
3
4
5
6
 
Selected barriers must have entity parameters such that  
Voc <
 
 V max, Isc < I max,  
Ca > Ci + Ccable, La > Li + Lcable. 
For Ccable and Lcable, if the capacitance per foot  
or the inductance per foot is not known, then the  
following values shall be used:  Ccable = 60pF/foot  
and Lcable = 0.2µH/foot. 
 
Contact current:  I max = 50mA 
 
Contact voltage:  V max. = 35V (DC or AC)  
Max. associated circuit capacitance Ci = 0  
Max. associated circuit inductance Li = 0     
No polarity requirement
 
 
June. 2010 / Rev. 1.3  DS-UB10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany