Puls UB10.241 UPS 사양 가이드
UB10.241
U–Series
24V, 10A, DC-UPS
25. I
NSTALLATION
N
OTES
Mounting:
The power terminal shall be located on top of the unit. An appropriate electrical and fire end-product enclosure
should be considered in the end use application.
The power terminal shall be located on top of the unit. An appropriate electrical and fire end-product enclosure
should be considered in the end use application.
Cooling: Convection cooled, no forced air cooling required. Do not obstruct air flow!
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended
when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance are
recommended.
when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance are
recommended.
Risk of electrical shock, fire, personal injury or death!
Turn power off and disconnect battery fuse before working on the DC-UPS. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit.
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where moisture or condensation can be expected.
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage
or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for
inspection!
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage
or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for
inspection!
Wiring and installation instructions:
(1) Connect the power supply to the input terminals of the DC-UPS.
(2) Connect the battery to the battery terminals of the DC-UPS. It is recommended to install the battery outside the
cabinet or in a place where the battery will not be heated up by adjacent equipment. Do not install the battery
in airtight housings or cabinets. The battery should be installed according to EN50272-2, which includes sufficient
ventilation. Batteries store energy and need to be protected against energy hazards. Use a 30A battery fuse typ
ATO® 257 030 (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery
and the DC-UPS. It also allows the disconnection of the battery from the DC-UPS which is recommended when
working on the battery or DC-UPS. Disconnect battery fuse before connecting the battery.
in airtight housings or cabinets. The battery should be installed according to EN50272-2, which includes sufficient
ventilation. Batteries store energy and need to be protected against energy hazards. Use a 30A battery fuse typ
ATO® 257 030 (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery
and the DC-UPS. It also allows the disconnection of the battery from the DC-UPS which is recommended when
working on the battery or DC-UPS. Disconnect battery fuse before connecting the battery.
Please note: Too small or too long wires between the DC-UPS and the battery can shorten the buffer time or can
result in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm
result in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm
2
(or 12AWG) and not longer than
2x1.5m (cord length 1.5m). Avoid voltage drops on this connection.
(3) Connect the buffered load to the output terminals of the DC-UPS. The output is decoupled from the input
allowing load circuits to be easily split into buffered and non buffered sections. Noncritical loads can be
connected directly to the power supply and will not be buffered. The energy of the battery can then be used in
the circuits which requires buffering.
connected directly to the power supply and will not be buffered. The energy of the battery can then be used in
the circuits which requires buffering.
(4) Install the fuse when the wiring is finished.
Fig. 25-1 Typical wiring diagram
24V
unbuffered
branch
24V
Power
supply
+
-
N
L PE
24V
buffered
branch
Buffered
load
+
-
Unbuffered
load
+
-
DC-UPS
UB10.241
24V
IN
24V
OUT
12V
BAT
+
-
+
-
+
-
12V
Battery
+
-
19/23
June. 2010 / Rev. 1.3 DS-UB10.241-EN
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current.
www.pulspower.com Phone +49 89 9278 0 Germany