Safety and Warning Information 
Important Notice  -  Before utilizing the product, the user should 
determine the suitability of the product for its intended use.  The 
user assumes all risk and liability in connection with such use.  
ULTRA ELECTRONICS’  WRITTEN WARRANTY FOR THE 
PRODUCT IS MADE IN LIEU OF ALL OTHER WARRANTIES, 
EXPRESSED OR IMPLIED WARRANTIES OF 
MERCHANTABILITY AND FITNESS FOR A PARTICULAR 
PURPOSE.  The user's exclusive remedy for breach of  Ultra 
Electronics' written warranty shall be the repair or replacement of 
such quantity of product which is proven to be defective.  In no 
case shall Ultra Electronics be liable for any special, incidental, or 
consequential damages based upon breach of contract, 
negligence, strict liability or other legal theory. 
Approval Agency Controlled Document 
No changes authorized without prior agency approval 
Publication Number: 
 
    RM0900202  Rev. 0 
Installation Instructions 
Original Instructions 
 
 
MX Multiplexer Base Modules 
 
For use ONLY with the  
EOTec MX Multiplexer Line 
 
Ultra Electronics 
N
UCLEAR SENSORS & PROCESS INSTRUMENATION 
707 Jeffery Way, PO Box 300 
Round Rock, TX 78680-300 USA 
Toll Free:   800-880-9333            
Telephone:  +1 512-434-2850 
Fax:  +1 512-434-2901 
Email:  fiberop@ultra-nspi.com 
www.ultra-nspi.com 
Ultra Electronics, Nuclear sensors & Process 
Instrumentation is a business name of Weed Instrument 
Co., Inc
 
 
When operating, do not look directly 
into the transmit optical port or use 
magnification or focusing equipment to 
view optical output. 
IEC 60825-1, Class 1 Laser Product 
FDA 21 CFR 1040.10 & 1040.11 
CAUTION: Use of controls and/or adjustments or the 
performance of procedures other than those 
specified herein may result in hazardous radiation 
exposure. 
 
Connect the DIN Rail, via the Model 
2A09 End Clamp, to Protective Earth 
(PE) ground with low impedance. 
ATEX Specific Conditions of Use 
Modules shall be installed in an enclosure which 
maintains an ingress protection rating of IP54 and meets 
the enclosure requirements of EN60079-0 and 
EN60079-15.  The EOTec modules shall be installed in 
DIN rail with DIN end clamps mounted on both sides of 
the module set.  The DIN rail must be connected to 
Protective Earth in order to provide modules with  a 
Protective Earth connection.  Do not disconnect 
equipment connections or modules when energized. 
 
 
 
 
Nuclear Sensors & 
Process Instrumentation 
 
Power:  At the top of the module, a pluggable screw 
terminal block is provided to apply power from a, 
nominal 24Vdc source.  The MX Base Module 
provides  this  received  power to all additional I/O 
modules connected via the 10+2  integrated BUS 
interconnection.  
Alarm Relay:  Also, at the  screw terminal block  are 
contacts of a Form-C (SPST) Alarm Relay which 
provide a remote fault indicator. There are four faults 
that will engage the relay: An I/O module mismatch, a 
loss of power, a loss of the optical signal, or a loss of 
the optical signal at remote receiver will set this alarm 
(engage relay). 
SFP:  MX Base modules use Small Form-factor 
Pluggable (SFP) transceivers with LC connectors.  
This replaceable transceiver determines the transmit 
and receive specifications of the MX Base module. 
 
Connections 
EOTec MX Multiplexer Models 
MXB-MM2 / MXB-SM15 
MXB-SM40 / MXB-SM80 
MX Base Modules 
 
Service 
 
Service of this equipment is to be performed by Ultra 
Electronics, NSPI only.  This unit has no scheduled 
replacement  of parts.  For installation manuals in a 
community language other than English please contact 
Ultra Electronics, NSPI.