PAN-14 Sensor Installation Guide 
 
3. 
Monitors the proper functioning of the sensors. See Panoramic Power 
Deployment Tool User Guide. 
Unpacking the Hardware 
Sensors are shipped in 3-unit packs.  
 
CTs are not included and can be bought separately. 
Safety Precautions 
 
The sensor must be installed only on an insulated conductor. 
 
CTs output/secondary current must not exceed 5A. 
 
The sensor and CT should be installed and removed only by a qualified 
electrician. 
 
Installation must not be performed on a live wire for reasons of safety 
and random shock hazard. Power supply to the panel must be shut off 
before and during installation. 
 
The sensor and CT must not be installed lying or touching bus
 
bars or 
any other non-insulated, exposed conductors. 
 
Installation is possible both on external entry/exit conductors before the 
terminal strip, as well as both ends of the circuit breaker. The least 
cramped, most accessible location should be chosen for installation. The 
sensor should be installed such that the arrow points in the direction of 
the load. 
Mapping the Site 
See Panoramic Power Deployment Guide.