PAN-42 User Guide 
 
Mapping the Site 
See Panoramic Power Deployment Guide. 
Installing the Sensor 
This procedure must be carried out by a certified electrician. 
1.  Make sure you connect the CTs through the shorting switches  
2.  Mount the CT(s) on the hot wire(s): 
a.  If the CT is split-core: Open the CT, and close it around the hot wire. 
b.  If the CT is solid-core: Disconnect one of the ends of the hot wire 
from the panel, insert it through the CT, and then reconnect it to the 
panel. 
c.  In both cases, make sure the CT is placed on the wire so that the 
direction of current flow on the wire is from the side marked "P1" or 
"K" on the CT, to the side marked "P2" or "L" on the CT. 
3.  Connect the three CTs to the inputs I1- I3, by performing the following 
procedure to all three CTs:  
a.  Use 1.0-4.0mm2 (12-17 AWG) wires. Make sure that the wire gauge is 
suitable for carrying 5Amms for the length of wire required, without 
a significant voltage drop. 
b.  Connect the PAN-42  sensor's terminal marked as "+" to the CT's 
terminal marked as "S1" or "K"  
c.  Connect the PAN-42 sensor's terminal marked as "–" to the CT's 
terminal marked as "S2" or "L"  
4.  Connect the voltage inputs: 
a.  Connect one to three phases L1, L2, L3 (R, S, T) and the neutral wire 
to the appropriate PAN-42 inputs, making sure each phase passes 
through an MCB (see Figure 2). 
b.  Make sure that you use the same phase for the current and voltage 
inputs; that is, L1 and I1 are for the same phase, L2 goes with I2, and 
L3 goes with I3.