Calculating Maximum Wiring Lengths
apC/8X Technical Manual
C
-
5
1a. Calculate Voltage Drop for RM A
Multiply 50 ft. * .1 A * .00879 = .04395 volts dropped for RM A
1b. Calculate Voltage Drop for RM B
Multiply (50 ft. + 500 ft.) *.1 A * .00879 = .48345 volts dropped
Multiply (550 ft.) *.1 A * .00879 = .48345 volts dropped for RM B
1c. Calculate Voltage Drop For RM C
Multiply (50 ft. + 500 ft. + 250 ft.) *.1 A * .00879 = .7032 Volts dropped
Multiply (800 ft.) *.1 A * .00879 = .7032 volts dropped for RM C
2. Add Voltage Drop for each Reader = Total Volts Dropped
Add .04395 (A) + .48345 (B) + .7032 (C) = 1.2306 Total Volts Dropped
3. Subtract Total Volts Dropped from Original Supply
12.0 VDC (original) - 1.2306 (volts dropped) = 10.7694 VDC remaining 
4. Is remaining voltage sufficient to operate the readers?
The RM-4 requires at least 7.5 volts to operate properly. 
All RM-4 readers in the chain must have at least 7.5 volts.
10.7604 volts is sufficient to power the RM-4 reader chain.