Method of Procedure 
Pre-Installation 
36 
RFN_3.1 Beta
 
System 
Unit 
Power 
 
 
Output 
Power Plant 
Rectifier 
Current 
 
20 Amperes/Rectifier for 100/120 
VAC 
 
30 Amperes/Rectifier for 200/240 
VAC 
  
Output 
Paralleling & 
Hot Insertion 
Each rectifier has an output o-ring diode 
in the –48 VDC lead for the purpose of 
paralleling and hot insertion in a working 
system. 
 Battery  105ah; 
VRLA 
3.3.5 Grounding 
System 
Unit 
Grounding 
Main Rack 
 
 
#2 AWG green-insulated copper wire between the main 
rack and the master ground bar 
 
do not daisy-chain multiple equipment cabinet grounds 
using a single ground wire 
RadioFrame System 
NCU 
 
internal grounding (UL and CE safety certified) 
 
bonding point provided for protective earth grounding; 
#8 screw with internal sems washer 
 ACU 
 
internal grounding (UL and CE safety certified) 
 
bonding point provided for protective earth grounding; 
#8 screw with internal sems washer 
iDEN Interface 
iSC-3  (1) 
#6 AWG ground wires are attached from the ground studs 
on the rear of the iSC-3 to the cabinet ground bus bar 
 
iSC-3  (2) 
#6 AWG ground wires are attached from the ground studs 
on the rear of the iSC-3 to the cabinet ground bus bar 
 
EAS 
#6 AWG ground wires are attached from the ground studs 
on the rear of the EAS to the cabinet ground bus bar 
 
CSU 
#6 AWG ground wires are attached from the ground studs 
on the rear of the CSU to the cabinet ground bus bar 
Power Plant 
Rectifier 
#6 AWG ground wires are attached from the ground studs 
on the rear of the Rectifier to the cabinet ground bus bar 
3.3.6 Environment 
Operating Ambient Temperature 
System 
Unit 
Storage Temp 
MIN 
MAX 
RadioFrame System 
NCU* 
-40ºF to +158ºF  
(-40ºC to +70ºC) 
+32ºF (0ºC) 
+104ºF (+40ºC) 
 
ACU* 
-40ºF to +158ºF  
(-40ºC to +70ºC) 
+32ºF (0ºC) 
+104ºF (+40ºC)