FinM Deployment Guide
Release 4.5.10
2‐50
TMU External Connections
Site Installation
2.5.6 TMU External Connections
Figure 2‐83: TMU ‐ External Connections
2.6 Grounding
All RADWIN products should be grounded during operation. In addition:
All units should be grounded by a wire with diameter of at least 10 AWG.
Units must be properly grounded to a Protective Ground in accordance with the Local 
Electrical Regulations
Rack‐mounted equipment should be mounted only in grounded racks and cabinets.
Further, you should ‐
Always make the ground connection first and disconnect it last
Never connect telecommunication cables to ungrounded equipment
Ensure that all other cables are disconnected before disconnecting the ground
TBS and OSU
There is a grounding lug on the TBS and OSU as shown in 
. Ground it using 10 AWG 
wire.