Controlled Electronic Management Systems Ltd INFOPROX 사용자 설명서
InfoProx Entry
Configuring the Door Control Unit
Relay Idle State
This screen indicates the idle/active state of the relay. In the following example,
the RO (Relay 0) is N/C (Normally Closed):
the RO (Relay 0) is N/C (Normally Closed):
Ù
Alter # Exit
RO N/C
If the reader has an exit connected, then the screen displays two relays (RO +
R1):
R1):
Ù
Alter # Exit
RO N/C R1 N/C
If the relays are set to N/O, the prompt
Ù
Alter #Exit
RO N/O R1 N/O
displays. N/O represents Normally Open.
The relay state facility is used to configure the reader for Powered to Secure or
Powered to Unlock operations, depending on the type of lock used.
Powered to Unlock operations, depending on the type of lock used.
To set the relays
1.
From the Configure Reader screen, press the # key six times or one time
from the Exit Configuration screen to continue to the Relay Idle State
prompt.
from the Exit Configuration screen to continue to the Relay Idle State
prompt.
2.
Press
Ù to set the relay as Normally Open.
3.
Press
Ù to set the relay to Normally Closed.
Note
Unit will reboot automatically if these settings are changed,
returning you to the main menu.
returning you to the main menu.