Controlled Electronic Management Systems Ltd INFOPROX 사용자 설명서

다운로드
페이지 79
InfoProx Entry   
 
Configuring the Door Control Unit 
Relay Idle State 
This screen indicates the idle/active state of the relay. In the following example, 
the RO (Relay 0) is N/C (Normally Closed): 
 
Ù
 Alter  # Exit 
RO N/C 
If the reader has an exit connected, then the screen displays two relays (RO + 
R1): 
 
Ù
 Alter  # Exit 
RO N/C  R1 N/C 
If the relays are set to N/O, the prompt 
 
Ù
 Alter  #Exit 
RO N/O  R1 N/O 
displays. N/O represents Normally Open. 
The relay state facility is used to configure the reader for Powered to Secure or 
Powered to Unlock operations, depending on the type of lock used.  
 
To set the relays 
1. 
From the Configure Reader screen, press the key six times or one time 
from the Exit Configuration screen to continue to the Relay Idle State 
prompt.   
2. 
Press 
Ù to set the relay as Normally Open
3. 
Press 
Ù to set the relay to Normally Closed
 
Note 
Unit will reboot automatically if these settings are changed, 
returning you to the main menu. 
 
 
Software House 
 
43