Series 5.0 Software (0510-1059-A_DRAFT) - User Guide
 81
Event Types
Check Transmitter Alarm 
The specified asset transmitter has not sent a signal to the system within the required time.
To respond to a Blue Check Transmitter Alarm
1.    Verify transmitter is applied correctly and without signs of damage.
2.    From the Client computer, click anywhere in the Check Transmitter Alarm Message Box to access the 
Event Information window.
3.    Select one of the following event causes: 
Test —the system was being tested.
Other—opens a Clear Reason window, user must enter the cause in this window.
You cannot clear an event until you select the appropriate cause for the event. The event is cleared from 
the Event List of every Client computer configured to monitor the unit.
4.    A Check Transmitter alarm may be an indication that Receiver coverage may be inadequate. Contact 
your System Administrator.
WARNING: You must test all transmitters prior to use to verify proper 
operation. Failure to test the transmitters before use can result in system failure 
and/or asset abduction. In addition, failure to test transmitters voids the RF 
Technologies Product Warranty.
N
OTE
You can click Silence to stop the alarm sound at the Central Server or Client 
computer. The alarm is silenced, at that computer only, for the configured length of time; 
however, the event still appears in the Event List. The next event automatically restarts the 
alarm sound.