• Check that the length of the L
ON
W
ORKS
 data cable corresponds to the 
norms indicated in Table 1. 
 
Type of cable 
Length [m] in relation to cable capacity 
AWG mm2 
Ohm/Km 
50nF/Km 
100nF/Km
200nF/Km
500nF/Km 
1uF/Km 
12 3,3 5,7 
2676 
1892 
1338 
846 598 
14 2 8,8 
2153 
1523 
1077 
681 
482 
16  1,3  14 1707 1207 854 540 382 
18  0,9  21 1394 986 697 441 312 
20  0,6  34 1096 775 548 346 245 
22 0,35 52  886 626 443 280 198 
24 0,2 85 693 490 346 219 155 
Table 1. Length/Capacity of L
ON
W
ORKS
 Data Cables (m) 
• The FTT10A Echelon
 v1.2 User Guide recommends the cables indicated 
in Table 2. 
Producer and Model 
AWG  Connection to 
bus -maximum 
total length [m] 
Connection in free 
topology
 –maximum 
node-node length 
max. [m] 
Connection in free 
topology
 –maximum 
total wire length. [m] 
Belden 85102 
16 
2700 
500 
500 
Belden 8471 
16 
2700 
400 
500 
Level IV (twisted-pair, 
typically solid and 
unshielded) 
22 1400 
400 
500 
JY (St) 2x2x0.8 (4-wire 
helical twist, solid 
shielded) 
20 900 
320 
500 
TIA Cat5 
900 
250 
450 
Table 2. Recommended LONWORKS
 Cables