Honeywell International Inc. TH8320EM01 사용자 설명서

다운로드
페이지 48
Home Energy Manager 
 
5 69-2537EFS—01
1H/1C System (1 transformer)
Rc 
Power 
[1]
[R+Rc joined by jumper]
Heat relay
Compressor contactor
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Heat Only System
Rc 
Power 
[1]
[R+Rc joined by jumper]
Heat relay
24VAC common
[3]
S1/S2 Optional outdoor sensor
Heat Only System (Series 20)
Rc 
[R+Rc joined by jumper]
Series 20 valve terminal “R”
[1]
Series 20 valve terminal “B”
Series 20 valve terminal “W”
24VAC common
[3]
S1/S2 Optional outdoor sensor
2H/2C System (1 transformer)
Y2 
Cool relay 2
W2 
Heat relay 2
Rc 
Power 
[1]
[R+Rc joined by jumper]
Heat relay 1
Cool relay 1
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
1H/1C System (2 transformers)
Rc 
Power (cooling transformer)
[1, 2]
Power (heating transformer)
[1, 2]
Heat relay
Compressor contactor
Fan relay
24VAC common
[3, 4]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Heat Only System With Fan
Rc 
Power 
[1]
[R+Rc joined by jumper]
Heat relay
Fan relay
24VAC common
[3]
S1/S2 Optional outdoor sensor
Cool Only System
Rc 
Power 
[1]
[R+Rc joined by jumper]
Compressor contactor
Fan relay
24VAC common
[3]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
2H/2C System (2 transformers)
Y2 
Cool relay 2
W2 
Heat relay 2
Rc 
Power (cooling transformer)
[1, 2]
Power (heating transformer)
[1, 2]
Heat relay 1
Cool relay 1
Fan relay
24VAC common
[3, 4]
Optional THP9045 Wiring Module Terminal
[9]
S1/S2 Optional outdoor sensor
Wiring guide—conventional systems
Wiring
See [
notes
] below
 [1] 
Power supply. Provide disconnect means and overload protection as required.
 [2] 
Remove jumper for 2-transformer systems.
 [3] 
Connection to 24VAC common at the transformer is required.
 [4]
Common connection must come from cooling transformer.
 [9]
See page 14 for more details.