Page 45
Configuration parameter
Descriptions
Address
Use the Address button to assign Silver Network based Senstar
LM100 gateway’s a unique network address (1 - 60)
LM100 gateway’s a unique network address (1 - 60)
Application
Use the Application button to update the LM100 gateway or
luminaire firmware
luminaire firmware
Config tab (sensor head configuration, settings apply to all luminaires)
Comm Channel
Comm Channel
If 2 or more Senstar LM100 systems operate within 400 m (1300 ft.)
of each other, they must use different Comm Channels to prevent
mutual interference
of each other, they must use different Comm Channels to prevent
mutual interference
Target Filter (Hz)
There are 2 Target Filters for adjusting the frequency response of
the luminaires (2 - 400 Hz)
The high pass filter is used to screen out low frequency vibrations
such as the fence motion caused by wind sway and loose fence
fabric
The low pass filter is used to screen out high frequency vibrations
such as the thermal expansion and contraction of palisade fences
the luminaires (2 - 400 Hz)
The high pass filter is used to screen out low frequency vibrations
such as the fence motion caused by wind sway and loose fence
fabric
The low pass filter is used to screen out high frequency vibrations
such as the thermal expansion and contraction of palisade fences
Event Window (sec)
Sets the time period after an Event is recorded before the next Event
can be recorded (0.5 - 10 seconds)
Used to prevent vibrations caused by a single Event from being
recorded as subsequent Events
can be recorded (0.5 - 10 seconds)
Used to prevent vibrations caused by a single Event from being
recorded as subsequent Events
Event Count
When the detection signal exceeds the Threshold setting an Event is
recorded and added to the Event Count;
When the number of recorded Events reaches the Event Count
setting an alarm is declared (1 - 10)
recorded and added to the Event Count;
When the number of recorded Events reaches the Event Count
setting an alarm is declared (1 - 10)
Alarm Window (sec)
Sets the time period after the first Event is recorded in which the
specified number of Events must occur to trigger an alarm
(1 - 99 seconds)
Each time the Event Count is incremented, the Alarm Window time
begins to count down from the set value;
If a subsequent Event occurs before the Alarm Window time lapses
the Event Count is incremented and the Alarm Window time begins
to count down from the set value;
If the Event Count setting is reached before the Alarm Window time
expires, a sensor alarm is declared;
The Alarm Window resets after each Event;
If the Alarm Window time lapses before a subsequent Event is
recorded both the Alarm Window time and the Event Count are reset
specified number of Events must occur to trigger an alarm
(1 - 99 seconds)
Each time the Event Count is incremented, the Alarm Window time
begins to count down from the set value;
If a subsequent Event occurs before the Alarm Window time lapses
the Event Count is incremented and the Alarm Window time begins
to count down from the set value;
If the Event Count setting is reached before the Alarm Window time
expires, a sensor alarm is declared;
The Alarm Window resets after each Event;
If the Alarm Window time lapses before a subsequent Event is
recorded both the Alarm Window time and the Event Count are reset
Normal Light Control - Set the luminaire brightness for routine scheduled operation
Light Level
Set the Light Level (brightness) for regularly scheduled light
activation (not alarm activation)
activation (not alarm activation)
Auto Light Control - Set the luminaire response to alarm conditions
Mode
Specify the luminaire’s lighting activity in response to a sensor alarm
(e.g., strobe the luminaire that recorded the alarm and activate all
luminaires that are assigned to the same zone)
(e.g., strobe the luminaire that recorded the alarm and activate all
luminaires that are assigned to the same zone)
Duration (min)
The number of minutes the activated luminaires will remain in alarm
mode following an alarm (1 - 15 minutes)
mode following an alarm (1 - 15 minutes)
Light Level
Set the Light Level (brightness) for alarm response light activation