SWH-4x00 models have twelve terminals as noted in Table 3. The terminal
strip is removable for easy installation and wiring. When attaching wires to
the connector, strip off only the minimum insulation required (approx. 1/
8'') and push the wire into the connector until the insulation is flush or
inside the connector body. This is particularly critical for outdoor readers.
While the reader itself is designed and protected to IP65 standards, the
cable wires can potentially corrode and short together if not carefully
mounted and tightly fastened in the connector body.
strip is removable for easy installation and wiring. When attaching wires to
the connector, strip off only the minimum insulation required (approx. 1/
8'') and push the wire into the connector until the insulation is flush or
inside the connector body. This is particularly critical for outdoor readers.
While the reader itself is designed and protected to IP65 standards, the
cable wires can potentially corrode and short together if not carefully
mounted and tightly fastened in the connector body.
Table 4 indicates maximum wiring distances per Wiegand standard with
the three most common gauges of cable.
the three most common gauges of cable.
TABLE 3. Connector Pins for Model SWH-4x00
Pin
Description
Pin
1
External Beeper Control
7
External Green LED Control
2
Ground
8
External Red LED Control
3
Power (8 to 16 VDC)
9
A - RS485 - used for Flash upgrade
4
D1 Wiegand
10
B - RS485 - used for Flash upgrade
5
D0 Wiegand
11
Tamper (Normally Closed)
6
Reserved for Future Use
12
Tamper (Normally Closed)
TABLE 4. Maximum cable distance for 18, 20, or 22 AWG wire
Wire Gauge
18 AWG
20AWG
22 AWG
Cable
Distance
Distance
500 feet
(152 meters)
(152 meters)
300 feet
(91 meters)
(91 meters)
200 feet
(61 meters)
(61 meters)