Mounting / Dismounting
9.1
Installation position 
The LCOS Unmanaged Switch, plugged onto an LCOS function carrier, is 
mounted vertically on a 35 mm DIN rail (TS 35). 
 
Risk of injury and damage to property from electric current. 
Current can injure persons and destroy the modules (assemblies).
▪ Disconnect the system from the power supply before assembly and 
disassembly.
With AC supply, an external overvoltage protection must limit the voltage 
between supply and VU to less than 1000 V.
For UL applications: Ambient temperature: +70°C
The module must be installed in a fire protection housing suitable for the end 
application. 
The device is intended to be used in indoor applications and be mounted 
in cabinets.
Ensure that the electrical installation complies with local or national 
safety regulations. 
Observe the minimum distances!
Mount the unit at a distance of at least 30 mm upwards and downwards (0 
mm to the side) from other units to ensure proper ventilation.