 Mounting / Dismounting
36
T R A N S P O R T A T I O N
9.3
Wiring
9.3.1
Safety notes Shielding ground
 
   
The device can be powered by function carrier LCOS-FT... to AC/DC24V, 
all voltages must be in conformance to SELV/PELV.
The conductor size has to be selected dependig on the load current and 
must be conform with international and national ruls and standards.
Attention! The supply cable must be suitable for an operating 
temperature range of -25 °C to +70 °C. 
The connecting cables must be designed for the ambient temperature. 
To ensure UL certification of the complete module, only use the plug-in 
terminals recommended by us. 
See also chapter "6.2 Accessories" on page 23)
A screwdriver is required for wiring. (e.g. slotted screwdriver 3 mm)
▪ Push-In terminal 
The shielding ground of the connectable twisted-pair cables is electrical-
ly conductively connected to the front panel. 
When operating the device via the plug-in terminal, connect the 
functional earth (FE) for proper functioning of the device. 
When connecting a cable segment with contacted shielding braid, check for 
possible ground loops. 
Stripping Length
Conductor Size
 
X9: 3-pole 
(RM/CS 5.08)
solid
0.08 ... 2.5 mm² 
AWG 28 – 12
X9: 3-pole 
(RM/CS 5.08)
fine stranded 
with ferrule
0.08 ... 2.5 mm²  
AWG 28 – 12