LCOS Unmanaged Switch 
 Commissioning - Hardware
41
T R A N S P O R T A T I O N
10
Commissioning - Hardware 
10.1
Safety notes Power supply      
The supply voltage is galvanically isolated from the housing. The devices can be 
supplied either via the energy bus X10 or the connection terminal X9. The power 
bus and the connection terminal are internally connected. Polarity is irrelevant. 
Commissioning of the hardware may only be carried out by qualified per-
sonnel in compliance with the safety regulations.
Only switch on a device when the housing is closed. 
Electric shocks and short-circuits due to incorrect voltage application.
Before commissioning, disconnect the entire system from the power supply and 
check the connections after applying power. 
The devices may only be connected to the supply voltage printed on the 
identification plate. 
The devices are designed for operation with safety extra-low voltage.
Accordingly, only SELV/PELV voltage circuits may be connected to the 
supply voltage connections.
The earth connection of the device serves exclusively as functional earth 
(FE) according to EN 61131-2. 
Make sure that peripherals are suitable for the application environment.
The connecting cables must be designed for the ambient temperature.
If the switches are supplied with AC, surge voltages of up to 2000 V can 
be expected between the active conductors and earth.
 
However, since the isolation voltage between functional earth (FE) and active 
conductors is only 1000 V, external overvoltage protection is required between 
the functional earth and at least one active conductor. 
This overvoltage protection must limit the voltage to 1000 V. 
Varistors of type 7N431K can be used for this purpose, for example.