Jinan USR IOT Technology Limited IO808 사용자 설명서

다운로드
페이지 25
                                    USR-IO808-EWR User Manual                                 
Technical Support
h.usriot.com
   
 
Jinan USR IOT Technology Limited                                                                                                                                     
www.usriot.com
 
 
11
 
2. Product function 
USR-IO808-EWR functional diagram as follow: 
Serial port 
device(Should 
support 
Modbus RTU 
protocl)
Network
server
Slave mode
Execute Modbus protocol   
RS485
Master mode
RTU check 
Data transparent 
transmission
RTU check 
Communication 
module
Modbus 
TCP/RTU 
protocol 
conversion
Input
Output
Switch/Button 
input
Relay output
 
Figure 12 Functional diagram 
2.1. DI input 
2.1.1. Electrical level detection 
➢ 
Register address range: 32~39(0x0020~0x0027) 
➢ 
Supported function code: 02(Read discrete input), 03(Read holding register) 
➢ 
Connection: Default is dry contact input. Short-circuit DI and COM will change input status. If user needs wet 
contact input can contact to our sales personnel 
➢ 
Electrical level detection: Default status is 0, after short-circuiting DI and COM, status will be 1. Detection 
method: 02 function code of Modbus protocol.   
 
Example:   
Detect input of the first way, send: 11 02 00 20 00 01 BA 90 
Short-circuiting will return: 11 02 01 01 64 88 
No short-circuiting will return: 11 02 01 00 A5 48 
2.1.2. Buttons detection 
➢ 
Register address range: 48~55(0x0030~0x0037) 
➢ 
Supported function code: 03(Read holding register), 04(Read input register) 
➢ 
Connection: Default is dry contact input. Short-circuit DI and COM will change input status. If user needs wet 
contact input can contact to our sales personnel 
➢ 
Electrical level detection: Default status is 0000, after short-circuiting DI and COM and then releasing, status 
will be FF00. Detection method: Read button register value by 03 function code of Modbus protocol. After 
reading once button register, status will recover to 0000; after executing conditional control, status will 
recover to 0000. too. 
 
Example:   
Detect the first way button, send: 11 03 00 30 00 01 86 95