Qolsys Inc. QS5210P01 사용자 설명서

다운로드
페이지 12
2
APD0597 A140618 Qolsys IQCO (QS-5210-PO1) Wireless CO Install Guide
The  IQCO  (QS-5210-PO1)  Wireless  Carbon  Monoxide  Alarm  contains  a 
sounder  which  generates  the  ANSI  S3.41  temporal  4  pattern  in  an  alarm 
condition (see Table 1 for temporal 4 pattern). In alarm, a message is also 
sent to the control panel and the detector’s ID is displayed at the console. 
During an alarm condition, pressing the detector’s hush button will silence 
the sounder for fi ve minutes. The mounting base installation is simplifi ed 
by the incorporation of features compatible for both drywall fasteners (not 
supplied) and other methods.
Tricolored LED (green, yellow, red) and a sounder on the detector provide 
local visual and audible indication of the detector’s status as listed in Table 1. 
During initial power-up the LED blinks alternately green, yellow then red. It 
takes about 60 seconds for the detector’s CO sensor to stabilize. 
After power-up has completed and the detector is functioning normally, the 
green LED blinks once every 12 seconds.
Status
LEDs
Sounder
(does not pulse 
the sounder and 
LED concurrently)
Radio
signalling
Normal
Green fl ash every 
12 seconds
Off
Normal
(None)
Alarm/ Test
Red fl ash every 
12 seconds
ANSI S3.41 
temporal 4 (press 
button to hush 
for 5 minutes)
Alarm
Detector
trouble
Yellow fl ash 
every 6 seconds
One 100ms chirp 
every 45 seconds
Fault
Low battery
Yellow fl ash 
every 12 seconds
One 100ms chirp 
every 45 seconds 
(press button 
to hush for 12 
hours)
Low Battery
Detector end 
of life
Yellow fl ash 
every 23 seconds
One 100ms chirp 
every 45 seconds
Fault
Powerup
Green, yellow, 
red fl ash 
sequence every 
12 seconds
One 100ms chirp 
at end of power-
up sequence
None
Tamper
Green, yellow, 
red fl ash 
sequence every 
12 seconds
Off
Tamper
Table 1. Detector status and indication