2.4.5  Functions of the jumpers      
 
JP5
- When in the upper position, the buzzer is enabled. 
 
JP15
- When set to the upper position, a request for RF testing mode is sent to the 
DREAM controller. (see paragraph 3.3 below about the RF test mode). 
3. 
THE VARIOUS  MODES OF OPERATION 
 
3.1 
START-UP MODE
  
 Right
 
after  energizing  the  RTU  or  after  pushing  it's  reset  button  there  is  an 
initialization  process  that  starts  with  a  sequence  of  3  short  and  one  long  beeps 

  after  which  the  solenoids  are  closed  one  by  one.  Every  15  seconds  2 
short beeps 

 
will be sounded and every 30 seconds the slave will try to acquire 
communication with the MASTER. During the process of acquiring communication 
the  red  LED 
  of  the  SLAVE  turns  on  indicating  that  the  receiver  is  open  and 
listening.  This  takes  about  10  seconds.  If  the  communication  is  established,  the 
RTU  goes  into  NORMAL  MODE,  otherwise  it  will  keep  trying  to  pick  up  the 
communication signal every 30 seconds.  
 
3.2 
NORMAL MODE
  
During  normal  mode  of  operation,  the  RTUs  are  scanned  by  the  host  via  the 
MASTER one by one in a cyclic manner and in a constant rate. In each cycle, every 
RTU is communicated within its allocated timeslot, which is dictated by its address. 
During that timeslot, an information exchange takes place, the required state of the 
outputs is sent from the host controller to the RTU, and the current state of inputs is 
transmitted back to the host controller. The rate of scanning must be identically set 
both  at  the  host  controller  and  at  each  RTU.  When  the  MASTER  initiates  a 
scanning cycle there will be a blink of the MASTER's LED 
 
and for each response 
received  correctly  from  any  RTU,  there  will  be  a  short  beep 
sounded  by  the 
MASTER's buzzer.  
At  the  other  end  the  RF  SLAVE  which  is  dormant  between  the  scanning  cycles, 
wakes  up  at  the  right  timeslot  and prepares itself for  receiving  the transmission  of 
the MASTER. This state is indicated by a blink of the SLAVE's LED 
.
 Each time a 
successful  information  exchange  takes  place  there  will  be  a  short  beep  sound 
made by the buzzers of both the RTU BASE and the RF SLAVE. If the RTU picks 
up  the  signal  from  the  MASTER  but  the  call  was  not  correctly  addressed,  it  will 
sound  a  double  beep 

.  For  those  who  have  difficulty  hearing  the  buzzer,  the 
green LED 
 
blinks each time the buzzer sounds. 
 
3.3 
RF TEST MODE
  
The  purpose  of  this  test  is  to  check  the  communication  quality  between  a  specific 
RTU and the MASTER. Prior to initiating the TEST mode, it must be enabled at the 
host controller. When enabled, the request for RF TEST is initiated from the RTU. 
By  setting  JP15  to  "RF  test"  (upper  position)  a  test  request  signal  is  sent  to  the 
Master.  When  the  request  is  received  by  the  MASTER,  it  is  immediately  granted 
and the RF test starts. During RF TEST mode the regular scanning of all the RTUs 
is  stopped  and  the  MASTER  starts  communicating  solely  with  the  RTU  under  test