Electrical Specifications: 
Frequency Range 
806-815MHz UL / 851-860MHz DL 
Maximum Gain (adjustable) 
92dB (Typ) 
Gain Adjustment, 1 dB steps. 
50dB to 92dB = 42dB total adjustment 
range 
Maximum Composite Output Power  
(i.e. single carrier) 
30dBm 
Power Limiter Adjustment (1dB increments)  30dBm to 16dBm 
Impedance 
50 Ohm 
Maximum RF Signal Input Level for FCC 
spurious limits compliance 
-20dBm 
Absolute Maximum Input RF Signal Level 
0dBm continuous, +10dBm peak 
Noise Figure 
<6.5dB typ.    8dB max. 
Alarms: 
Two Form C relays for each of the alarms: 
AC Power Status, Charger Status, Low 
Battery Capacity, Low Battery Voltage, BDA 
Trouble, Antenna Trouble and Aux Alarm. 
Second relay contact set provided for a LED 
annunciator panel.   
Alarm Logging: 
Standard SD Card up to 16GB. Mini SD with 
adaptor. Real-time clock time stamp 
included. 
AC Power Supply 
Two independent power supplies with 110-
240VAC/2.1A or 277VAC/0.8A 50/60Hz 
each. 
Power Supply Efficiency 
93% (Typ.) 
DC Power Supply 
Supports either 2x75Ah 12V AGM Sealed 
L.A. Batteries in series for DC UPS Backup 
or an external 28VDC Supply. Max. Current 
Draw: 2.3A @ 28VDC 
Run Time with standard 2x75Ah Battery 
Backup 
>25-30 Hours under full load 
Battery Charging with the Built-in 
Charger** 
Charging Current Limited to 5A max. Float 
voltage: 27.4V  
Operating Temperature Range 
-30°C to +65°C 
Recommended Ambient Temperature*** 
-20°C to +35°C (-4°F to +95°F) 
 
 
 
 
 
** Only use approved lead-acid batteries. Contact RSI for list of approved batteries.  
*** Extended ambient temperatures and outdoor applications may require specialized 
enclosures. Please inquire with your specific requirements.  
*** Operating the device outside the recommended ambient temperature range may void 
the warranty.