Moog Videolarm SPVRJ01 전단

다운로드
페이지 2
www.videolarm.com
S P V R J 0 1
Video Surge Protection
Installation and Operation Instructions for the following model:
81-IN5403
12-23-2011
SPVRJ01
Data/power over ethernet power/data surge protection
Before attempting to connect or operate this product, please read these instructions completely.
© 2011, Moog Videolarm, Inc. All Rights Reserved
This Surge Protection Device (SPD) is a high performance device, designed to provide protection for sensitive electronic loads connected to service panels, fire panels, or where the
SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed by a qualified electrician in accordance with the National and Local Electrical Codes and the following instructions.
APPLICATION
Surge suppression for POE circuits using CAT 5e cable and RJ45 connectors.
INSTRUCTIONS:
Caution:
Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit. Improper installation voids the warranty. This unit must be connected in series
with the equipment to be protected.
NOTE: Data pins: 1- 2, 3 - 6 and power pins: 4 - 5, 7 - 8
1. Connect the incoming wires to the “IN” connector.
2. Connect a CAT 5e patch cable from the “OUT” to the equipment to be protected.
3. Use one common ground per system to eliminate the possibility of a differential in ground potentials. Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less
is optimum. This cannot be an assumed value and must be measured to assure proper grounding.
4. For mounting, use double sided tape (supplied), or two (2) #8 screws (not supplied).