Table  5
!!!
AIC,  Fuse  and  Wire  sizes 
Voltage
class 
Applicable 
motor 
  [kW] 
Inverter model
UL   
output current
(A)    *2, *3 
AIC (A) 
(Interrupting 
capacity) 
Fuse class 
and current
(A) 
Input wire sizes of 
power circuit 
*4 
Output wire sizes of 
power circuit 
*4 
Earth 
*4 
200V
class 
0.4 
VFAS1-2004PL
2.5 (EH=) 
AIC  5000A 
CC 7Amax. 
AWG  14 
AWG  14 
AWG  14 
0.75 
VFAS1-2007PL
4.8 (EH=) 
AIC  5000A 
J 15Amax. 
AWG  14 
AWG  14 
AWG  14 
1.5 
VFAS1-2015PL
7.8 (EH=) 
AIC  5000A 
J 25Amax. 
AWG  14 
AWG  14 
AWG  14 
2.2 
VFAS1-2022PL
11.0 (EH=) 
AIC  5000A 
J 25A max. 
AWG  12 
AWG  12 
AWG  14 
3.7/4.0 
VFAS1-2037PL
17.5 (EH=) 
AIC  5000A 
J 45Amax. 
AWG  10 
AWG  10 
AWG  12 
5.5 
VFAS1-2055PL
25.3 (EH=) 
AIC  5000A 
J 60Amax. 
AWG  8 
AWG  8 
AWG  10 
7.5 
VFAS1-2075PL
32.2 (EH=) 
AIC  5000A 
J 70Amax. 
AWG  8 
AWG  8 
AWG  10 
11 
VFAS1-2110PM
48.3 (EH=) 
AIC  5000A 
J 90Amax. 
AWG  4 
AWG  4 
AWG  10 
15 
VFAS1-2150PM
62.1 (EH=) 
AIC  5000A 
J 110Amax. 
AWG  4 
AWG  4 
AWG  10 
18.5 
VFAS1-2185PM
74.8 (EH=.)
AIC  5000A 
J 125Amax. 
AWG  3 
AWG  3 
AWG  8 
22 
VFAS1-2220PM
88 (EH=.) 
AIC  5000A 
J 150Amax. 
AWG  2 
AWG  2 
AWG  8 
30 
VFAS1-2300PM
114 (EH=.)
AIC  5000A 
J 200Amax. 
AWG  2/0 
AWG  2/0 
AWG  6 
37 
VFAS1-2370PM
143 (EH=.)
AIC  5000A 
J 225Amax. 
AWG  3/0 
AWG  3/0 
AWG  6 
45 
VFAS1-2450PM
169 (EH=.)
AIC  10000A
J 300Amax. 
AWG  4/0 
AWG  4/0 
AWG  6 
55 
VFAS1-2550P 
221 (EH=.)
AIC  10000A
J 350Amax. 
AWG  3/0  ×  2 
AWG  3/0  ×  2 
AWG  2 
75 
VFAS1-2750P 
285 (EH=.)
AIC  10000A
J 450Amax. 
AWG  4/0  ×  2 
250MCM  ×  2 
AWG  2 
400V
class 
0.75 
VFAS1-4007PL
2.1 (EH=) 
AIC  5000A 
CC 6Amax. 
AWG  14 
AWG  14 
AWG  14 
1.5 
VFAS1-4015PL
3.4 (EH=) 
AIC  5000A 
CC 12Amax. 
AWG  14 
AWG  14 
AWG  14 
2.2 
VFAS1-4022PL
4.8 (EH=) 
AIC  5000A 
J 15Amax. 
AWG  14 
AWG  14 
AWG  14 
3.7/4.0 
VFAS1-4037PL
7.6 (EH=) 
AIC  5000A 
J 25Amax. 
AWG  12 
AWG  12 
AWG  14 
5.5 
VFAS1-4055PL
11.0 (EH=) 
AIC  5000A 
J 40Amax. 
AWG  10 
AWG  10 
AWG  12 
7.5 
VFAS1-4075PL
14. 0 (EH=) 
AIC  5000A 
J 40Amax. 
AWG  10 
AWG  10 
AWG  12 
11 
VFAS1-4110PL
21.0 (EH=) 
AIC  5000A 
J 60Amax. 
AWG  8 
AWG  8 
AWG  10 
15 
VFAS1-4150PL
27.0 (EH=) 
AIC  5000A 
J 70Amax. 
AWG  6 
AWG  6 
AWG  10 
18.5 
VFAS1-4185PL
34.0 (EH=) 
AIC  5000A 
J 70Amax. 
AWG  6 
AWG  6 
AWG  10 
22 
VFAS1-4220PL
40.0 (EH=) 
AIC  5000A 
J 80Amax. 
AWG  6 
AWG  6 
AWG  10 
30 
VFAS1-4300PL
52.0 (EH=) 
AIC  5000A 
J 90Amax. 
AWG  4 
AWG  4 
AWG  10 
37 
VFAS1-4370PL
65.0 (EH=.)
AIC  5000A 
J  110Amax. 
AWG  3 
AWG  3 
AWG  8 
45 
VFAS1-4450PL
77.0 (EH=.)
AIC  10000A
J  150Amax. 
AWG  1 
AWG  1 
AWG  8 
55 
VFAS1-4550PL
96.0 (EH=.)
AIC  10000A
J  175Amax. 
AWG  1/0 
AWG  1/0 
AWG  6 
75 
VFAS1-4750PL
124.0 (EH=.) 
AIC  10000A
J  225Amax. 
AWG  3/0 
AWG  3/0 
AWG  6 
90 
VFAS1-4900PC
179.0 (EH=.) 
AIC  10000A
J  250Amax. 
AWG  1/0  ×  2 
250  MCM  ×  2  *1 
AWG  1/0  ×  2 
250  MCM  ×  2  *1 
AWG  2 
250  MCM  *1 
110 
VFAS1-4110KPC
215.0 (EH=.) 
AIC  10000A
J  300Amax. 
AWG  3/0  ×  2 
250  MCM  ×  2  *1 
AWG  3/0  ×  2 
250  MCM  ×  2  *1 
AWG  2 
250  MCM  *1 
132 
VFAS1-4132KPC
259.0 (EH=.) 
AIC  10000A
J  350Amax. 
AWG  4/0  ×  2 
250  MCM  ×  2  *1 
AWG  4/0  ×  2 
250  MCM  ×  2  *1 
AWG  1 
250  MCM  *1 
160 
VFAS1-4160KPC
314.0 (EH=.) 
AIC  18000A
J  400A  max. 
300  MCM  ×  2 
350  MCM  ×  2  *1 
300  MCM  ×  2 
350  MCM  ×  2  *1 
AWG  1 
250  MCM  *1 
200 
VFAS1-4200KPC
387.0 (EH=.) 
AIC  18000A
J  500Amax. 
AWG  4/0  ×  3 
350  MCM  ×  3  *1 
AWG  4/0  ×  3 
350  MCM  ×  3  *1 
AWG  1/0 
250  MCM  ×  2  *1
220 
VFAS1-4220KPC
427.0 (EH=.) 
AIC  18000A
J  500Amax. 
250  MCM  ×  3 
350  MCM  ×  3  *1 
250  MCM  ×  3 
350  MCM  ×  3  *1 
AWG  2/0 
250  MCM  ×  2  *1
280 
VFAS1-4280KPC
550.0 (EH=.) 
AIC  18000A
T  700Amax. 
350  MCM  ×  3 
350  MCM  ×  3  *1 
350  MCM  ×  3 
350  MCM  ×  3  *1 
AWG  3/0 
250  MCM  ×  2  *1
355 
VFAS1-4355KPC
671.0 (EH=.) 
AIC 30000A
J 450A × 2 max.
400  MCM  ×  2  ×  2 
500 MCM × 2 × 2 *1
400  MCM  ×  4 
500  MCM  ×  4  *1 
AWG  4/0 
500  MCM  *1 
400 
VFAS1-4400KPC
759.0 (EH=.) 
AIC 30000A
J 500A × 2 max.
500  MCM  ×  2  ×  2 
500 MCM × 2 × 2 *1
500  MCM  ×  4 
500  MCM  ×  4  *1 
AWG  4/0 
500  MCM  *1 
500 
VFAS1-4500KPC
941.0 (EH=.) 
AIC 42000A
J 600A × 2 max.
400  MCM  ×  3  ×  2 
500 MCM × 3 × 2 * 1
400  MCM  ×  5 
500  MCM  ×  5  *1 
250  MCM 
500  MCM  *1 
*1: This part shows the wiring size with using the Lug terminal. 
The Lug terminals are an option. 
*2: UL output current is different from unit rating output current. 
*3: The value of the UL rated output current is applicable when the carrier frequency (EH) is less than the value 
shown in the table. 
*4: The cables used must be 75°C copper cables with in 40°C ambient temperature. 
9.2.4  Caution  as  to  the  protection  of  motors  from  overload!!!!
When using the inverter’s thermal protection function to protect the motor from overload, read the instruction manual 
included with the inverter carefully and set parameters according to the specifications of the motor used. 
When using the inverter to control the operation of multiple motors, install an overload relay for each individual motor.