102
Table 5-4
Filter Data
Panel-Type Filters
Bag-Type Filters
Cartridge Filters
Panel-Type Prefilters
Unit Model
(Note 1)
(Note 2)
(box-type) (Note 2)
(Note 3)
Qty
Size of each
Qty.
Size of each
Qty.
Size of each
Qty.
Size of each
S_HF-C20 &
12
20 X 20 X 2
4
12 X 24 X 19
4
12 X 24 X 12
4
12 X 24 X 2
C25
3
24 X 24 X 19
3
24 X 24 X 12
3
24 X 24 X 2
S_HF-C30
16
20 X 20 X 2
2
12 X 24 X 19
2
12 X 24 X 12
2
12 X 24 X 2
6
24 X 24 X 19
6
24 X 24 X 12
6
24 X 24 X 2
S_HF-C40
16
20 X 25 X 2
5
12 X 24 X 19
5
12 X 24 X 12
5
12 X 24 X 2
6
24 X 24 X 19
6
24 X 24 X 12
6
24 X 24 X 2
S_HF-C50 &
20
20 X 25 X 2
3
12 X 24 X 19
3
12 X 24 X 12
3
12 X 24 X 2
C55
9
24 X 24 X 19
9
24 X 24 X 12
9
24 X 24 X 2
S_HF-C60,
35
16 X 20 X 2
6
12 X 24 X 19
6
12 X 24 X 12
6
12 X 24 X 2
C70 & C75
8
24 X 24 X 19
8
24 X 24 X 12
8
24 X 24 X 2
S_HG-C90 &
25
24 X 24 X 2
3
12 X 24 X 19
3
12 X 24 X 12
3
20 X 24 X 2
S_HG-D11
15
24 X 24 X 19
15
24 X 24 X 12
15
24 X 24 X 2
S_HG-D12 &
25
24 X 24 X 2
3
12 X 24 X 19
3
12 X 24 X 12
3
20 X 24 X 2
S_HG-D13
15
24 X 24 X 19
15
24 X 24 X 12
15
24 X 24 X 2
Notes:
1.  Dimensions shown for “Panel-Type Filters”apply to “Throw away”, “Cleanable Wire Mesh”,
    and “High Efficiency Throw away” Filters.
2.  S_HF units ordered with “Bag-Type Filters” or “Cartridge Filters” (box-type) include a bank
    of “Panel-Type Prefilters”.
3.  The same “Panel-Type Prefilters” are used with “Bag-Type” and “Cartridge (box-type)” filters.
Table 5-5
"Wet Heat" Coil Fin Data
Total Coil
Fins
Fins
Coil
Coil
Face Area
per
per
Model
Type
Rows
(sq.ft.)
Foot
Foot
SLHF-C20,
WC
C25 & C30
Prima Flo
2
13.75
80
110
(hot water)
SLHF-C40,
WC
C50 & C55
Prima Flo
2
19.25
80
110
(hot water)
SLHF-C60,
WC
C70 & C75
Prima Flo
2
26.25
80
110
(hot water)
SLHG-C90,
WC
D11, D12
Prima Flo
2
17.5 (2)
80
110
& D13
(hot water)
SSHF-C20,
NS
1
13.75
42
96
C25 & C30
(steam)
SSHF-C40,
NS
1
13.75 (1)
42
96
C50 & C55
(steam)
5.5 (1)
SSHF-C60,
NS
1
18.75 (1)
42
72
C70 & C75
(steam)
7.5 (1)
SLHG-C90,
NS
1
17.5 (2)
52
96
D11, D12
(steam)
& D13
Note: To determine unit heating capacity (i.e., “low heat” or “high heat”),
see Digit 9 of the model number stamped on the unit nameplate.