General Information (Continued)
Variable Air Volume (VAV) Units
Occupied Heating - Supply Air Temperature
When a VAV units is equipped with "Modulating Heat", and
the system is in an occupied mode, and the field supplied
changeover relay contacts (5K87) have closed, the supply
air temperature will be controlled to the customer specified
supply air heating setpoint. It will remain in the heating sta-
tus until the changeover relay contacts are opened.
Occupied Cooling - Supply Air Temperature
When a VAV unit is in the occupied mode, the supply air
temperature will be controlled to the customers specified
supply air cooling setpoint by modulating the economizer
and/or staging the mechanical cooling "On and Off" as re-
quired. The changeover relay contacts must be open on
units with "Modulating Heat" for the cooling to operate.
Daytime Warm-up
On VAV units equipped with heat, if the zone temperature
falls below the daytime warm-up initiate temperature dur-
ing the occupied mode, the system will switch to  full air-
flow. During this mode, the VAV box/unocc relay, RTM K3,
will be energized (this is to signal the VAV boxes to go to
100%).  After the VAV box max stroke time has elapsed
(factory set at 6 minutes), the VFD/IGV output will be set to
100%.  The airflow will be at 100% and the heat will be
turned on to control to the occupied heating setpoint.
When the zone temperature reaches the daytime warm-up
termination setpoint, the heat will be turned off, the K3 re-
lay will be de-energized, releasing the VAV boxes, the
VFD/IGV output will go back to duct static pressure control
and the unit will return to discharge air control. If the occ
zone heating setpoint is less than the DWU terminate
setpoint, the heat will turn off when the occ zone heat
setpoint is reached, but it will stay in DWU mode and cycle
the heat to maintain setpoint.
Unoccupied Heating - Zone Temperature
When a VAV unit is equipped with gas, electric, or hydronic
heat and is in the unoccupied mode, the zone temperature
will be controlled to within the customers specified setpoint
deadband.  During an unoccupied mode for a VAV unit, the
VAV box/unocc relay will be in the unoccupied position and
the VFD/IGV output will be at 100%.  This means that if
there is a call for heat (or cool) and the supply fan comes
on, it will be at full airflow and the VAV boxes in the space
will need to be 100% open as signaled by the VAV box/
unocc relay.
Supply Air Tempering
On VAV units equipped with "Modulating Heat", if the sup-
ply air temperature falls 10
 
F below the supply air tempera-
ture setpoint, the hydronic heat valve will modulate to
maintain the supply air temperature to within the low end
of the setpoint deadband.
Supply Duct Static Pressure Control (Occupied)
The RTM relies on input from the duct pressure transducer
when a unit is equipped with Inlet Guide Vanes or a Vari-
able Frequency Drive to position the Inlet Guide Vanes or
set the supply fan speed to maintain the supply duct static
pressure to within the static pressure setpoint deadband.
Refer to the Transducer Voltage Output vs Pressure Input
values listed in the Space Pressure Transducer (3U62)
section.
Unit Component Layout and "Shipwith" Locations