Installation (Continued)
Table 3-4
Sizing Natural Gas Pipe Mains & Branches
Sizing Natural Gas Pipe Mains & Branches
Gas Input (Cubic Feet/Hour)*
Notes: 
1. If more than one unit is served by
Gas Supply
1-1/4" 1-1/2"
   2"
2-1/2"
   3"
   4"
    the same main gas supply, consider
Pipe Run (ft)
Pipe
Pipe
Pipe
Pipe
Pipe
Pipe
    the total gas input (cubic feet/hr.)
10
1050
1600
3050
4800
8500 17500
    and the total length when determining
20
730
1100
2100
3300
5900 12000
    the appropriate gas pipe size.
30
590
890
1650
2700
4700
9700
2. Obtain the Specific Gravity and 
40
500
760
1450
2300
4100
8300
    BTU/Cu.Ft. from the gas company.
50
440
670
1270
2000
3600
7400
3. The following example demonstrates
60
400
610
1150
1850
3250
6800
    the considerations necessary when
70
370
560
1050
1700
3000
6200
    determining the actual pipe size.
80
350
530
990
1600
2800
5800
90
320
490
930
1500
2600
5400
Example: A 40' pipe run is needed to 
100
305
460
870
1400
2500
5100
connect a unit with a 500 MBH furnace to a
125
275
410
780
1250
2200
4500
natural gas supply having a rating of 1,000
150
250
380
710
1130
2000
4100
BTU/Cu.Ft. and a specific gravity of 0.60
175
225
350
650
1050
1850
3800
200
210
320
610
980
1700
3500
Cu.Ft/Hour = Furnace MBH Input
* Table is based on a specific gravity of 0.60. Use Table 3-1 for         Gas BTU/Cu.Ft. X Multiplier (Table 3-1)
   specific gravity of the local gas supply. 
                      Cu.Ft/Hour = 500 
Table 3 indicates that a 1-1/4" pipe  is required.
Specific Gravity Multipliers
Specific
Gas Heating Capacity Altitude Correction Factors
Gravity
     Multiplier
0.50
         1.10
     Sea Level        2001        2501        3501         4501        5501         6501
0.55
         1.04
      To 2000      To 2500   To 3500   To 4500   To 5500   To 6500   To 7500
0.60
         1.00
Capacity
0.65
         0.96
Multiplier       1.00              .92             .88             .84             .80            .76            .72
Note: Correction factors are per AGA Std. 221.30 - 1964, Part VI, 6.12.
           Local codes may supersede.
      Altitude (Ft.)
Figure 3-10
Unit Gas Trains (Natural Gas)
235 and 350 MBH
500 and 850 MBH