Trane RT-SVX10C-EN 사용자 설명서

다운로드
페이지 118
62
Table 4-1 (Continued)
Service Test Guide for Component Operation
COMPONENT
COMPONENT CONFIGURATION 
Occ
BEING TESTED
Supply Exhaust Condenser Heat Stages
Compressor Stage
Econo Exhaust
VFD
Unocc
(Cont.)
Fan
Fan
Fans
1
2
3
1
2
3
4
Damper Damper
IGV
Output Relay
** CONDENSER FANS
 90 Ton
1A-2B3/2B14
Off
Off
1A-On/1B-Off Off Off Off K11-Off K3-Off K12-On K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B1/2B2
Off
Off
1A-Off/1B-On Off Off Off K11-On K3-Off K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A-2B6/2B13
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B4/2B5
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-On
   105 & 115 Ton
1A-2B3/2B14
Off
Off
1A-On/1B-Off Off Off Off K11-Off K3-Off K12-On K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B1/2B2/2B19
Off
Off
1A-Off/1B-On Off Off Off K11-On K3-Off K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-Off
2A-2B6/2B13
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-Off K12-Off K4-On Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B4/2B5/2B15
Off
Off
1A-Off/1B-Off Off Off Off K11-Off K3-On K12-Off K4-Off Closed
Closed Closed
0%
Default
2A-Off/2B-On
   130 Ton
1A-2B3/2B14
Off
Off
1A-On/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-Off/2B-Off
1B-2B1/2B2
Off
Off
1A-Off/1B-On Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
  2B19/2B20
2A-Off/2B-Off
2A-2B6/2B13
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
2A-On/2B-Off
2B-2B4/2B5
Off
Off
1A-Off/1B-Off Off Off Off
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
  2B15/2B21
2A-Off/2B-On
SUPPLY FAN
On
Off
All Off
Off Off Off
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
EXHAUST FAN
Off
On
All Off
Off Off Off
Off
Off
Off
Off
Closed
100%
100%
100% Default
Open
Open
GAS HEAT (Full Cap.)
On
Off
All Off
On On N/A
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Stage 1
On
Off
All Off
On Off N/A
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Stage  2
On
Off
All Off
Off On N/A
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Full Modulating
On
Off
All Off
90% Select
Off
Off
Off
Off
Closed
Closed
100%
100%
Unocc
 (High Fire Adjustment)
Open
Full Modulating
On
Off
All Off
5% Select
Off
Off
Off
Off
Closed
Closed
100%
100%
Unocc
 (Low Fire Adjustment)
Open
Limited Modulating
On
Off
All Off
90% Select
Off
Off
Off
Off
Closed
Closed
100%
100%
Unocc
 (High Fire Adjustment)
Open
Limited Modulating
On
Off
All Off
33% Select
Off
Off
Off
Off
Closed
Closed
100%
100%
Unocc
 (Low Fire Adjustment)
Open
ELECTRIC HEAT
On
Off
All Off
On On On
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Stage 1
On
Off
All Off
On Off Off
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Stage  2
On
Off
All Off
Off On Off
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Stage  3
On
Off
All Off
Off Off On
Off
Off
Off
Off
Closed
Closed
100%
100% Unocc
Open
Hydronic Heat
Off
Off
All Off
100% Select
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
Pre - Heater
Off
Off
All Off
On N/A N/A
Off
Off
Off
Off
Closed
Closed Closed
0%
Default
Fresh Air Dampers
Off
Off
All Off
Off Off Off
Off
Off
Off
Off
100%
Closed Closed
0%
Default
Open
Exhaust Dampers
Off
Off
All Off
Off Off Off
Off
Off
Off
Off
100%
100%
Closed
0%
Default
Open
* - Compressors for the 20 thru 60 Ton units can operate individually or together and in any order while in the SERVICE TEST mode.
Compressors 1A &1B and compressors 2A & 2B operate simultaneously within their respective circuits on the 70 thru 105 Ton units. 
Compressors 1A & 1B, 1C & 1D, 2A & 2B, 2C & 2D operate simultaneously within their respective circuits on 115 and 130 Ton units.
Caution: Do Not operate the compressors for extended periods of time without the condenser fans, High Head Pressure will develope.
** - Condenser fan outputs can operate individually or together and in any order while in the SERVICE TEST mode.
*** - Once the unit has started, refer to the Status Menu in the Human Interface for the OA CFM.
**** - RTM OCC/UNOCC output in the Service Test Mode must be in the unoccupied mode to open the system VAV boxes and the 
Inlet Guide Vanes or to drive the VFD to 100%.