Table 4-6 (Continued)
115 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt; "On")
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
180
200
220
240
260
280
300
320
340
360
380
50
55
60
65
70
75
80
85
90
95
100
SUCTION PRESSURE, PSIG
DISCHARG
E PRESSURE, PSIG
105 F OD Ambient 
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
    entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
    next to the compressor.
4. Plot the outdoor dry bulb temperature and the 
    operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
    discharge pressure. The measured discharge
    pressure should be within ± 7 psig of the graph.
130 Ton Operating Pressure Curve (All Compressors and Condenser Fans, per ckt;
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
180
200
220
240
260
280
300
320
340
360
380
50
55
60
65
70
75
80
85
90
95
100
SUCTION PRESSURE, PSIG
DISCHARG
E PRESSURE, PSIG
105 F OD Ambient 
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
    entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
    next to the compressor.
4. Plot the outdoor dry bulb temperature and the 
    operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
    discharge pressure. The measured discharge
    pressure should be within ± 7 psig of the graph.