XR500 Series Canadian Programming Guide
32
bell oPTionS
Bell Options
10.1 
 
   BELL OPTIONS
 
Bell Options
This section allows you to program the panel bell output functions.   
10.2 
 
BELL CUTOFF:  15
 
Bell Cutoff Time
Enter the maximum time from 1 to 99 minutes the Bell Output remains on. If the
area is disarmed, the cutoff time resets. Enter 0 (zero) to provide continuous bell
output.  The default is 15 minutes.  
Note: To support the Alarm Verify feature on an All/Perimeter or Home/Sleep/Away
system, set the Bell Cutoff Time to greater than 0.
Note: For SIA CP-01 False Alarm Reduction Installations, the Bell Cutoff Time must 
be set to a minimum of six (6) minutes.
10.3 
 
BELL TST    NO   YES
 
Automatic Bell Test 
Select YES to turn on the Bell Output for 2 seconds each time the system
 
is 
com pletely armed from a 
keypad. This test is delayed until the Closing Wait
acknowledge is received (if programmed). If the Closing Wait acknowledge is not
received within 90 seconds, the bell test does not occur. Arming performed from an
Arming zone or from Remote Link™ does not activate the Bell Test.
10.4    
BELL OUTPUT:        0
 
Bell Output
Enter the output number when needed to follow the panel Bell Output operation for
all action and off conditions. Enter 0 (zero) to disable.
Note: When BELL ACTION is set to T for Temporal Code 3, the Bell Output action for
an LX-Bus output is pulse.
10.5 
 
BELL ACTION . . . . . 
 
Bell Action
This section defines the type of Bell Output for zone alarms. Press COMMAND to
display the default Bell Output for each zone type. Press any Select key and enter
S for a Steady Bell Output, P for a Pulsed output, T for a Temporal Code 3 output,
and N for no Bell Output.
Note: Trouble conditions do not activate the Bell Output.
10.5.1   
FIRE    TYPE:       P
 
Fire Bell Action
Defines Bell Action for Fire Type zones. The default is P.
10.5.2   
BURGLARY TYPE:   S
 
Burglary Bell Action
Defines Bell Action for Burglary Type zones and Exit Error output. The default is S.
10.5.3   
SUPRVSRY TYPE:    N
 
Supervisory Bell Action
Defines Bell Action for Supervisory Type zones. The default is N.
10.5.4   
PANIC    TYPE:       N
 
Panic Bell Action
Defines Bell Action for Panic Type zones. The default is N.
10.5.5   
EMERGNCY TYPE:        N
 
Emergency Bell Action
Defines Bell Action for Emergency Type zones. The default is N.
10.5.6   
AUXLRY  1 TYPE:     N
 
Auxiliary 1 Bell Action
Defines Bell Action for Auxiliary 1 Type zones. The default is N.
10.5.7   
AUXLRY 2 TYPE:     N
 
Auxiliary 2 Bell Action
Defines Bell Action for Auxiliary 2 Type zones. The default is N.