Lapara LA-ON-1K-LCD 사용자 설명서
www.laparaups.com
LA-ON-RACK
Technical specifications
LA-ON-RACK SERIES ON-LINE UPS
MODEL
LA-ON-1K-R (L)
LA-ON-2K-R (L)
LA-ON-3K-R (L)
LA-ON-6K-R (L)
LA-ON-10K-R (L)
CAPACITY
1000VA/800W
2000VA/1600W
3000VA/2400W
6000VA / 4800W
10000VA/8000W
INPUT
Low Line Transfer
80/70/60/50VAC ±5% or 160/140/120/110VAC ±5%
176VAC ±3 @ 100% load
110VAC ±3 @ 50% load
Low Line comeback
85/75/65/55VAC ±5% or 170/150/130/120VAC ±5%
186VAC @ 100% load
120VAC @ 50% load
High Line Transfer
150VAC ±5% or 300VAC ±5%
300VAC ±3%
Voltage
Range
Range
High Line comeback
145VAC ±5% or 290VAC ±5%
290VAC ±3%
Frequency Range
45~55Hz or 56~65Hz
46~54Hz or 56~64Hz
Phase
Single phase with ground
Power Factor
≧ 0.99
≧ 0.99 @ 100% load
OUTPUT
Output voltage
Output voltage
110/115/120/127VAC or 208/220/230/240VAC
208/220/230/240 VAC
AC Voltage Regulation (Batt. Mode)
± 1%
Frequency Range
(Synchroniz.Range)
(Synchroniz.Range)
48~52Hz or 58~62Hz
46~54Hz@50Hz / 56~64Hz @60Hz
Frequency Range (Batt. Mode)
50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio
3:1
Harmonic distortion
≦ 2% THD (Linear Load)
8% max (Battery mode before shutdown)
≦ 3% THD (Linear Load)
≦ 6% THD (Non-Linear load)
AC to Batt. Mode
Zero
Transfer Time
Inverter to Bypass
4 ms (Typical)
Zero
Waveform (batt. Mode)
Pure Sine Wave
EFFICIENCY
AC Mode
AC Mode
86%
88%
89%
Battery Mode
83%
85%
88%
BATTERY
Battery type
12V/7AH 12V/9AH 12V/7AH 12V/9AH
12V/ 9AH
12V/7AH
12V/9AH
Number
3* (LV)
2
6* (LV)
4
6
20
20
Typical Recharge Time
4 hours recover to 90% capacity
3h. up to 90% cap. 4h. up to 90% cap.
Max. charging current
1.0 A
2.0 A
Standard
Model
Model
Charging voltage
41.1
VDC
27.4
VDC
82.1
VDC
54.8
VDC
82.1
VDC
273.0 VDC ±1%
Battery type
Depending on applications
Number
Depending on the capacity of external batteries
18-20
Max. charging current
8.0 A
2.0 A
Long-run
Model
Model
Charging voltage
41.1
VDC
27.4
VDC
82.1
VDC
54.8
VDC
82.1
VDC
273.0 VDC ±1%
INDICATORS
LCD Panel
LCD Panel
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer and Fault
ALARM
Battery Mode
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
CONNECTORS
Power Output
8xIEC
6xIEC + TB
2xIEC + Terminal Block
Communication Ports
1xUSB + 1xRS232 + 1xRJ45
1xUSB + 1xRS232 + 1xRJ45
PHYSICAL
Dimensions
DxWxH (mm)
DxWxH (mm)
480x438x
88
380x438x
88
600x438x
88
480x438x
88
600x438x88 [2U]
UPS:580x438x133
Batt: 580x438x133
Batt: 580x438x133
UPS:668x438x133
Batt: 580x438x133
Batt: 580x438x133
Standard
Model
Model
Net Weight (Kg)
18,4 (LV)
13,2
25,7 (LV)
20,6
29
UPS: 17
Battery: 57
UPS: 20
Battery: 63
Dimensions
DxWxH
DxWxH
480x438x
88
380x438x
88
600x438x
88
480x438x
88
600x438x88 [2U] 580x438x133 [3U] 668x438x133 [3U]
Long-run
Model
Model
Net Weight (Kg)
11,3 (LV)
9,1
14,6 (LV)
11,3
14,8
17
20
ENVIRONMENT
Power Output
Power Output
20-90 % RH @ 0- 40°C (non-condensing)
Communication Ports
< 45dBA @ 1 m.
< 55dB @ 1 m.
< 58dB @ 1 m.
MANAGEMENT
Smart RS-232 & USB
Smart RS-232 & USB
Supports Windows 98 SE/ME/NT 4.x/2000/2003/XP/Vista/2008/7, Linux, Unix and Mac
SNMP optional
Power management from SNMP manager and web browser
* Specifications are subject to change without furher notice. / * L means long-run model
* In LV system, only 12V/7Ah x 3 for 1K model and 12V/7Ah x 6 for 2K model are available.
Note 1: Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC
Note 2: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
* In LV system, only 12V/7Ah x 3 for 1K model and 12V/7Ah x 6 for 2K model are available.
Note 1: Derate capacity to 60% of capacity in CVCF mode and to 90% when the output voltage is adjusted to 208VAC
Note 2: If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated one percent per 100m.
- 20 -