The power cord must have an IEC 320/EN60320 female connector on one 
end.

The cordage must be harmonized to CENELEC publication HD-21. The 
electrical characteristics and rating must be minimum H05VVF3G1.00 (10 A).
E
NVIRONMENTAL
 S
PECIFICATIONS
This section describes the following environmental specifications for the 
library.
G
ENERAL
 E
NVIRONMENTAL
 S
PECIFICATIONS
 lists general environmental specifications for the library. 
Table A-5 Environmental specifications
Specification
Operating
a
Storage
b
 or 
Non-Operating
c
Transportation
d
Ambient 
Temperature Range
+10° C to +40° C
e
(+50° F to +104° F)
–40° C to +65° C
(–40° F to +150° F)
–40° C to +65° C
(–40° F to +150° F)
Temperature
Variation
f
(Thermal Gradient)
1° C per minute;
max 10° C per hour
(2° F per minute;
max 18° F per hour)
1° C per minute;
max 20° C per hour
(2° F per minute;
max 36° F per hour)
1° C per minute;
max 20° C per hour
(2° F per minute;
max 36° F per hour)
Relative Humidity
20% to 80%
Non-condensing
10% to 90%
Non-condensing
10% to 90%
Non-condensing
Wet Bulb
26° C (79° F) max
29° C (84° F) max
29° C (84° F) max
Altitude
–306 m to +3,048 m
(–1,004 ft to +10,000 ft)
–306 m to +3,048 m
(–1,004 ft to +10,000 ft)
–306 m to +12,192 m
(–1,004 to +40,000 ft)
a
These measurements assume that the library is installed in accordance with the instructions in this manual.
b
The library is in its original packaging. The packaging is designed to protect the library from condensation caused by extreme temperature 
variations (15° C or more). When the library is moved from a cold storage environment to a warm operating environment, it must be 
acclimated in its packaging for at least 12 hours before opening to prevent serious condensation damage from occurring.
c
The library has been unpacked.
d
The library has not been unpacked. The transportation period does not exceed 72 hours.
e
The upper ambient operating temperature limit of +40° C (+104° F) is specified at +914.4 m (+3,000 feet), derated linearly to +24° C 
(+75.2° F) at +3,048 m (+10,000 feet).
f
The data cartridges’ temperature and humidity must be allowed to stabilize in the specified ambient environment for 24 hours.