9. Installation Instruction 
9.1  Select the Best Location 
9.1.1 Indoor 
Unit 
•  There should not be any heat source or steam near the 
unit.  
•  There should not be any obstacles blocking the air 
circulation. 
•  A place where air circulation in the room is good. 
•  A place where drainage can be easily done. 
•  A place where noise prevention is taken into consideration. 
•  Do not install the unit near the door way.  
•  Ensure the spaces indicated by arrows from the wall, ceiling, 
fence or other obstacles. 
•  Recommended installation height for indoor unit shall be at 
least 2.5m. 
9.1.2 Outdoor 
Unit 
•  If an awning is built over the unit to prevent direct sunlight or 
rain, be careful that heat radiation from the condenser is not 
obstructed. 
•  There should not be any animal or plant which could be 
affected by hot air discharged. 
•  Keep the spaces indicated by arrows from wall, ceiling, 
fence or other obstacles. 
•  Do not place any obstacles which may cause a short circuit 
of the discharged air. 
•  If piping length is over the rated length, additional refrigerant 
should be added as shown in the table below: 
 
 
 
 
 
 
 
 
 
Example: If the unit is installed at a 10m distance, the quantity 
of additional refrigerant should be 50 g. 
…… (10-7.5) m x 20g/m = 50 g 
 
 
 
 
 
 
Piping size 
Model 
Gas Liquid 
Rated 
Length 
(m) 
Max 
Elevati
on (m)
Min 
Piping 
Length 
(m) 
Max 
Piping 
Length 
(m) 
Additional 
Refrigera
nt (g/m) 
UE9JKE 3/8” 
1/4"  7.5 
15 
20 
UE12JKE 3/8” 1/4” 
7.5 
15 
20 
11.1.3 Indoor/Outdoor Unit