10. Error codes
When detecting an operating state which is not permissible, the device will display an error code
The following error codes are defined:
Err.1:
Exceeding of the measuring range
Indicates that the valid measuring range of the device has been exceeded.
Possible causes:
- Temperature too high.
- sensor broken.
- sensor is wrong connected
Remedies:
- The error-message will be reset if the input signal is within the limits.
- check probe and device configuration.
Err.2:
Value below the measuring range
Indicates that the value is below the valid measuring range of the device.
Possible causes:
- Temperature is too low
- sensor shorted
- sensor is wrong connected
Remedies:
- The error-message will be reset if the input signal is within the limits.
- check probe and device configuration.
Err.7:
System-error
The device features an integrated self-diagnostic-function which checks essential parts of the de-
vice permanently. When detecting a failure, error-message Err.7 will be displayed.
Possible causes:
- Valid operating temperature range has been exceeded or is below the
 valid temperature range.
- Device defective.
Remedies:
- Stay within valid temperature range.
- Exchange the defective device.
Err.9:
Sensor defective
The device features a built in diagnose function for the connected probe or transducer.
When this function is detecting an error the message Err.9 will be displayed.
Possible causes:
- probe broken or shorted
- sensor is wrong connected
Remedies:
- check probe and exchange defective probe, if necessary.
Er.11: Value could not be calculated
Indicates a measuring value, needed for calculation of the display value, is faulty or out of range.
Possible causes:
- one input signal has transgressed the measuring range or is not
   connected
Remedies:
- check probe and exchange defective probe, if necessary.